OVERVIEW OF UNITS
2-1. SYSTEM CONSTRUCTION
Connectable indoor unit lineup
Model type
Model name
P10 P15
P20 P25 P32
P40
P50 P63
P71 P80 P100 P125 P140
P200 P250
1-way cassette
PMFY-P·VBM-E
●
●
●
●
2-way cassette
PLFY-P·VLMD-E
●
●
●
●
●
●
●
●
●
4-way cassette
PLFY-EP·VEM-E *
3
●
●
PLFY-M·VEM-E
●
●
●
●
●
●
●
●
●
PLFY-P·VEM-E
●
●
●
●
●
●
●
●
●
PLFY-P·VEM-PA
●
●
●
●
●
●
●
2 by 2
PLFY-P·VFM-E1
●
●
●
●
●
●
Ceiling concealed
PEFY-P·VMS1(L)-E
●
●
●
●
●
●
●
PEFY-P·VMA3-E *
4
●
●
●
PEFY-P·VMHS-E
●
●
●
●
●
●
●
●
●
●
PEFY-P·VMR-E-L/R
●
●
●
PEFY-M·VMA(2)(L)-A
●
●
●
●
●
●
●
●
●
●
●
PEFY-P·VMA(L)-E1
●
●
●
●
●
●
●
●
●
●
●
PEFY-P·VMA(L)-E3
●
●
●
●
●
●
●
●
●
●
●
PEFY-P·VMH-E/E2
●
●
●
●
●
●
●
●
●
●
PEFY-P·
VMX(L)-E(1)
●
●
●
●
●
●
●
Ceiling suspended PCFY-P·VKM-E
●
●
●
●
Wall mounted
PKFY-P·VKM-E
●
●
PKFY-P·VLM-E
●
●
●
●
●
●
●
Ceiling concealed
(Fresh air type) *1
PEFY-P·VMHS-E-F
●
Floor standing
PFFY-P·VLEM-E
●
●
●
●
●
●
PFFY-P·VKM-E2
●
●
●
●
PFFY-P·VCM-E
●
●
●
●
●
●
Rossnay*5
GUF-·
RD(H)4
●
●
Note: The lineup of a connectable indoor unit depends on a district/areas/country.
Outdoor unit
10HP
12HP
P250YBM
P300YBM
Applicable
indoor unit
Capacity
Type 10 to Type 250
Number of units
1 to 30 units
Total system capacity range
50 to 130 % of outdoor unit capacity
(14.0 to 36.4 kW)
50 to 130 % of outdoor unit capacity
(16.8 to 43.5 kW)
M series remote
controller
M series indoor unit
*2
MSZ-EF Series
MSZ-FH Series
MSZ-LN Series
MFZ-KT Series
MSZ-AP Series
CONNECTION KIT
PAC-LV11M-J
Branching pipe
components
CMY-Y62-G-E
CMY-Y64-G-E
CMY-Y68-G-E
Branch header
(2 branches)
Branch header
(4 branches)
Branch header
(8 branches)
Remote
controller
Name
M-NET remote controller
MA remote controller
Model number
PAR-F27MEA-E, PAR-U02MEDA
PAR-4xMAA, PAR-3xMAA ("x"
represents 0 or later)
Functions
· A handy remote controller for use
in conjunction with the Melans
centralized management system.
· Addresses must be set.
·Address setting is not necessary.
*1 PUMY is connectable to Fresh Air type indoor unit. It is possible to connect 1 Fresh Air type indoor unit to 1 outdoor unit. (1:1
system) Operating temperature range (outdoor temperature) for fresh air type indoor units differ from other indoor units. Refer
to "2-4-(3). Operating temperature range".
*2 When connecting the CONNECTION KIT (PAC-LV11M-J) and an M-series indoor unit, refer to the installation manual for the
CONNECTION KIT. Refer to the connectable indoor unit lineup in "2-2 SYSTEM CONSTRUCTION (BRANCH BOX SYSTEM)
for connectable indoor unit models.
*3 Authorized connectable indoor units are only as follows:
PUMY-P250 : PLFY-EP63VEM-E × 4
PUMY-P300 : PLFY-EP50VEM-E × 1 + PLFY-EP63VEM-E × 4
*4 Authorized connectable indoor units are only as follows:
PUMY-P250 : PEFY-P63VMA3-E × 4
PUMY-P300 : PEFY-P80VMA3-E × 1 + PEFY-P71VMA3-E × 3
*5 Do not connect Lossnay remote controller(s). (PZ-61DR-E, PZ-60DR-E, PZ-52SF-E, PZ-43SMF-E)