background image

S1

S2

S3

S1

S2

S3

8

6. Electrical work

 Warning:

In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power 
line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power 
is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.

A-Control

Outdoor Unit

3 pole isolator

Power supply

Isolator

A-Control

Indoor Unit

7. Test run

7.1. Before test run

   After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power supply 
or control wiring, wrong polarity, and no disconnection of one phase in the 
supply.

   Use a 500-volt megohmmeter to check that the resistance between the pow-

er supply terminals and ground is at least 1 M

"

.

   Do not carry out this test on the control wiring (low voltage circuit) termi-

nals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1 M

"

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 
period, the insulation resistance will drop below 1 M

"

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 M

"

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3.  After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 
measure the insulation resistance again.

 •  

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

"

 after the compressor is warmed 

up for 4 hours.

     (The time necessary to warm up the compressor varies according to atmos-

pheric conditions and refrigerant accumulation.)

 •  

To operate the compressor with refrigerant accumulated in the compressor, 
the compressor must be warmed up at least 12 hours to prevent breakdown.

4.  If the insulation resistance rises above 1 M

"

, the compressor is not faulty.

 Caution:

•  

The compressor will not operate unless the power supply phase connection 
is correct.

•  

Turn on the power at least 12 hours before starting operation.

-  

Starting operation immediately after turning on the main power switch can result 
in severe damage to internal parts. Keep the power switch turned on during the 
operational season.

   The followings must be checked as well.

•  

The outdoor unit is not faulty. LED1 and LED2 on the control board of the outdoor 
unit 

fl

 ash when the outdoor unit is faulty.

•  

Both the gas and liquid stop valves are completely open.

•  

A protective sheet covers the surface of the DIP switch panel on the control board 
of the outdoor unit. Remove the protective sheet to operate the DIP switches eas-
ily.

7.2. Test run

7.2.1. Using SW4 in outdoor unit

SW4-1

ON

Cooling operation

SW4-2

OFF

SW4-1

ON

Heating operation

SW4-2

ON

*  After performing the test run, set SW4-1 to OFF.
•  

After power is supplied, a small clicking noise may be heard from the inside of the 
outdoor unit. The electronic expansion valve is opening and closing. The unit is 
not faulty.

•  

A few seconds after the compressor starts, a clanging noise may be heard from 
the inside of the outdoor unit. The noise is coming from the check valve due to the 
small difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW4-2 during 
the test run. (To change the test run operation mode during the test run, stop 
the test run by DIP switch SW4-1. After changing the test run operation mode, 
resume the test run by switch SW4-1.)

7.2.2. Using remote controller

Refer to the indoor unit installation manual.

6.2. Field electrical wiring

Outdoor unit model

P100,125V

P140V

P100, 125, 140Y

Outdoor unit power supply

~/N (single), 50 Hz, 230 V

~/N (single), 50 Hz, 230 V

3N~ (3 ph 4-wires), 

50 Hz, 400 V

Outdoor unit input capacity Main switch (Breaker)

*1

32 A

40 A

16 A

Wiring 

Wire No. × 

size (mm

2

) Outdoor unit power supply

3 × Min. 4

3 × Min. 6

5 × Min. 1.5

Indoor unit-Outdoor unit

*2

3 × 1.5 (Polar)

3 × 1.5 (Polar)

3 × 1.5 (Polar)

Indoor unit-Outdoor unit earth

*2

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 1.5

Remote controller-Indoor unit

*3

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

Circuit rating

Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)

*4

AC 230 V

AC 230 V

AC 230 V

Indoor unit-Outdoor unit S1-S2

*4

AC 230 V

AC 230 V

AC 230 V

Indoor unit-Outdoor unit S2-S3

*4

DC 24 V

DC 24 V

DC 24 V

Remote controller-Indoor unit

*4

DC 12 V

DC 12 V

DC 12 V

*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
 

Make sure that the current leakage breaker is one compatible with higher harmonics.

 

Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.

 

The use of an inadequate breaker can cause the incorrect operation of inverter.

*2. Max. 45 m
 

If 2.5 mm

2

 used, Max. 50 m

 

If 2.5 mm

2

 used and S3 separated, Max. 80 m

*3. The 10 m wire is attached in the remote controller accessory.
*4.  The 

fi

 gures are NOT always against the ground.

 

S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national code.
      2.  Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed 

fl

 exible cord. (Design 60245 IEC 57)

      3.  Install an earth longer than other cables.

Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a 

fi

 re or communication failure.

Summary of Contents for PUHZ-P HA Series

Page 1: ...amente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado El idioma original del documento es el inglés Las versiones en los demás idiomas son traducciones del original MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il cond...

Page 2: ... and moisture enter the unit electric shock or fire may result When installing or relocating or servicing the outdoor unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may...

Page 3: ...r compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use a vacuum pump with a reverse flow check valv...

Page 4: ...ition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 ...

Page 5: ...rate thermal insulation for gas and liquid refrigerant pipes The indoor parts of the drain pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut A Use 2 wrenches to tighten piping connections B Use leak detector or soapy water to check fo...

Page 6: ...kgf cm G wait 5 minutes and make sure the pres sure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease the pipes have passed the test and there are no leaks If the surrounding temperature changes by 1 C the pressure will change by about 0 03 MPa 0 3 kgf ...

Page 7: ... Additional refrigerant charging amount 21 30 m 31 40 m 41 50 m P100 50 m 30 m 0 6 kg 1 2 kg 1 8 kg P125 P140 0 6 kg 1 2 kg 4 Installing the refrigerant piping 4 7 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 8 A Indoor unit B Outdoor unit C Multi distribution pipe option D Height difference Indoor unit Outdoor unit Max 30 m E ...

Page 8: ...top valves are completely open A protective sheet covers the surface of the DIP switch panel on the control board of the outdoor unit Remove the protective sheet to operate the DIP switches eas ily 7 2 Test run 7 2 1 Using SW4 in outdoor unit SW4 1 ON Cooling operation SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small click...

Page 9: ...of wiring 2 A Outdoor unit B Indoor unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 8 1 3 Because the unit automatically stops in about 2 to 3 minutes when the refrigerant collecting operation i...

Page 10: ... The serial number is indicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 4 2015 5 ...

Page 11: ...оком или возникновению пожара При установке перемещении или сервисном обслуживании наружного блока используйте только указанный хладагент R410A для заправки трубопроводов хладагента Не смешивайте его ни с каким другим хлада гентом и не допускайте наличия воздуха в трубопроводах Наличие воздуха в трубопроводах может вызывать скачки давления в результате которых может произойти взрыв или другие повр...

Page 12: ...ы хладагента может произойти порча масла или поломка компрессо ра Используйте в качестве масла охлаждения для покрытия соединительных муфт масло сложного или простого эфира или алкинбензол в небольшом количестве Если в масле охлаждения присутствует минеральное масло может произойти порча масла Используйте только хладагент R410A В случае использования другого хладагента хлор может испортить масло И...

Page 13: ... друга Не используйте дополнительные воздуховоды для восходящего потока воздуха 3 Окружающие предметы только спереди Fig 2 14 При использовании дополнительного воздуховода выходного отверстия расстояние для моделей P125 P140 должно быть 1000 мм или более 4 Окружающие предметы только спереди и сзади Fig 2 15 При использовании дополнительного воздуховода выходного отверстия расстояние для моделей P1...

Page 14: ...ливайте тепловую изоляцию отдельно на трубы с газо образным и жидким хладагентом Внутренняя часть дренажной трубы должна быть обернута в пенополиэтиле новый изолирующий материал удельный вес 0 03 толщина 9 мм или более Нанесите тонкий слой масла хладагента на контактную поверхность труб и соединений перед тем как затягивать гайку с фланцем A Для затягивания трубных соединений используйте два гаечн...

Page 15: ...4 15 МПа 41 5 кгс см G и измерьте температуру окружающего воздуха и давление хладагента 3 Если указанное давление держится в течение приблизительно одного дня и не уменьшается то трубы выдержали испытание и утечек нет При изменении температуры окружающего воздуха на 1 C давление изменя ется приблизительно на 0 03 МПа 0 3 кгс см G Произведите необходимые подстройки 4 Если на этапах 2 или 3 наблюдае...

Page 16: ...ладагента для зарядки 21 30 м 31 40 м 41 50 м P100 50 м 30 м 0 6 кг 1 2 кг 1 8 кг P125 P140 0 6 кг 1 2 кг 4 Прокладка труб хладагента 4 7 Для комбинации двух трех блоков Ограничение по длине и разность высоты при прокладке труб показаны на ри сунке Fig 4 8 A Внутренний прибор B Наружный прибор C Распределительная труба опция D Разность высоты Внутренний прибор Наружный прибор макс 30 м E Разность ...

Page 17: ...ора Для облегчения работы с DIP переключателями удалите защитный лист 7 2 Выполнение испытания 7 2 1 Использование SW4 в наружном блоке SW4 1 ON Вкл Работа в режиме охлаждения SW4 2 OFF Выкл SW4 1 ON Вкл Работа в режиме обогрева SW4 2 ON Вкл После выполнения пробного прогона установите SW4 1 на OFF Выкл После подачи питания внутри наружного прибора могут появиться шумы лег кие щелчки Это работа эл...

Page 18: ... двойная утроенная выполнение электропроводки 2 не требуется A Наружный прибор B Внутренний прибор C Главный пульт дистанционного управления D Подчиненный пульт дистанционного управления E Стандарт 1 1 Адрес хладагента 00 F Одновременный двойник Адрес хладагента 01 G Одновременный тройник Адрес хладагента 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 8 1 3 Поскольку прибор авт...

Page 19: ...Последовательные номера для каждого устройства 00001 99999 Месяц изготовления A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Год изготовления западный календарь 2014 4 2015 5 Название компании ООО Мицубиси Электрик РУС Адрес Россия 115054 Москва Космодамианская наб д 52 стр 1 ...

Page 20: ...00 500 1000 400 600 1000 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 100 200 200 300 100 200 150 250 150 250 1000 1500 300 500 Max 500 100 150 500 1000 Unit mm P125 P140 ...

Page 21: ...ομηχανικές εφαρμογές através da presente declara sob sua única responsabilidade que os aparelhos de ar condicionado e bombas de calor abaixo descritos para uso residencial comercial e de indústria ligeira Série PUHZ P YHA é concebida para aplicações comerciais e industriais ligeiras erklærer hermed under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyg...

Page 22: ...6 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer ...

Reviews: