17
OCH724
17
Check code
Symptom
Remark
P1
Intake sensor error
P2
P9
E6, E7
Indoor/outdoor unit communication error
P6
Freezing/Overheating safeguard operation
EE
Communication error between indoor and outdoor units
P8
Pipe temperature error
E4
Controller signal receiving error
FL
Refrigerant leakage
FH
Refrigerant sensor error
PL
Refrigerant circuit abnormal
– –
No corresponding
Indoor unit fan motor error
[Output pattern A] Errors detected by indoor unit
• On controller
Check code displayed in the LCD.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
Check code
Symptom
Remark
E9
For details, check the LED
display of the outdoor controller
board.
UP
Compressor overcurrent interruption
U3, U4
Open/short of outdoor unit thermistors
UF
U2
U1, Ud
U5
Abnormal temperature of heat sink
U8
Outdoor unit fan safeguard stop
U6
Compressor overcurrent interruption/Abnormal of power module
U7
Abnormality of super heat due to low discharge temperature
U9, UH
Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/
Current sensor error
Other errors (Refer to the technical manual for the outdoor unit.)
Others
• If the unit cannot be operated properly after test run has been performed, refer to the following table to remove the cause.
Indicates whether control power is supplied. Make sure that this LED is always lit.
Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
indoor unit which is connected to the outdoor unit refrigerant address “0”.
Indicates state of communication between the indoor and outdoor units. Make sure that this LED is
always blinking.
Symptom
Cause
Controller
PLEASE WAIT
For about 3 min-
utes following
power-on
After LED1, 2 are lighted, LED2 is turned
off, then only LED1 is lighted. (Correct
• For about 3 minutes following power-on, operation of the
controller is not possible due to system start-up. (Correct
PLEASE WAIT
→
Error code
After about 3
minutes has
expired following
power-on
Only LED1 is lighted.
→
LED1, 2 blink.
• Connector for the outdoor unit’s protection device is not
connected.
• Reverse or open phase wiring for the outdoor unit’s power
Display messages do not appear even
when operation switch is turned ON
Only LED1 is lighted.
→
LED1 blinks twice,
LED2 blinks once.
• Incorrect wiring between indoor and outdoor units (incorrect
• Remote controller wire short
Error code