Mitsubishi Netcom User Manual
Rev 3 02/24/2009
52
::= { upsConfig 5 }
upsConfigOutputPower OBJECT-TYPE
SYNTAX
NonNegativeInteger
-- UNITS Watts
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The magnitude of the nominal true power rating (watts)."
::= { upsConfig 6 }
upsConfigLowBattTime OBJECT-TYPE
SYNTAX
NonNegativeInteger
-- UNITS minutes
ACCESS
read-write
STATUS
mandatory
DESCRIPTION
"The value of upsEstimatedMinutesRemaining at which a
lowBattery condition is declared.
For agents which
support only discrete (discontinuous) values, then the
agent shall round up to the next supported value.
If
the requested value is larger than the largest
supported value, then the largest supported value
shall be selected."
::= { upsConfig 7 }
upsConfigAudibleStatus OBJECT-TYPE
SYNTAX
INTEGER
{
disabled(1),
enabled(2),
muted(3)
}
ACCESS
read-write
STATUS
mandatory
DESCRIPTION
"The requested state of the audible alarm.
When in
the disabled state, the audible alarm should never
sound.
The enabled state is self-describing.
Setting
this object to muted(3) when the audible alarm is
sounding shall temporarily silence the alarm.
It will
remain muted until it would normally stop sounding and
the value returned for read operations during this
period shall equal muted(3).
At the end of this
period, the value shall revert to enabled(2).
Writes
of the value muted(3) when the audible alarm is not
sounding shall be accepted but otherwise shall have no
effect."
::= { upsConfig 8 }
upsConfigLowVoltageTransferPoint OBJECT-TYPE
SYNTAX
NonNegativeInteger
-- UNITS RMS Volts
ACCESS
read-write
STATUS
mandatory
DESCRIPTION
"The minimum input line voltage (RMS Volts) allowed before
the UPS system transfers to battery backup."
::= { upsConfig 9 }