background image

En-11

When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.

1) Turn off the breaker.

2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.

3) Fully close the stop valve on the liquid pipe side of the outdoor unit.

4) Turn on the breaker.

5) Start the emergency COOL operation on all the indoor units.

6) When the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm

2

), fully close the stop valve on the gas pipe side of the outdoor unit and 

stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)

  * If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.05 MPa [Gauge] (approx. 0.5 kgf/cm

2

), or the protection 

function may operate due to the pressure increase in the high-pressure refrigerant circuit. If this occurs, use a refrigerant collecting device to collect all of 

the refrigerant in the system, and then recharge the system with the correct amount of refrigerant after the indoor and outdoor units have been relocated.

7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.

When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.

The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.

 WARNING

5.  PUMPING DOWN

VG79A985H01_01En.indd   11

2018/10/03   11:45:09

Summary of Contents for MXZ-3HA50VF

Page 1: ...ão Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidade interior consulte o manual de instalação da unidade interior Installationshåndbog Til INSTALLATØREN Denne håndbog beskriver kun hvordan udendørsenheden installeres Vedrørende installation af indendørsenheden henvises til installationshåndbogen for indendørsenheden Installations...

Page 2: ...і а потім мову BG Посетете горепосочения уебсайт за да изтеглите ръководства като изберете име на модел и след това език PL Odwiedź powyższą stronę internetową aby pobrać instrukcje wybierz nazwę modelu a następnie język CS Příručky naleznete ke stažení na internetové stránce zmíněné výše poté co zvolíte model a jazyk SK Na webovej stránke vyššie si môžete stiahnuť návody Vyberte názov modelu a zv...

Page 3: ...ation ventilate the room Check that the refrigerant does not leak after installation has been completed If refrigerant leaks and comes in contact with fire or heating part of such a fan heater kerosene heater or cooking stove it will create harmful gas Provide ventilation in accordance with EN378 1 Check that the refrigerant gas does not leak after installation has been completed If refrigerant ga...

Page 4: ...LECTING THE INSTALLATION LOCATION Where it is not exposed to strong wind Where airflow is good and dustless Where rain or direct sunshine can be avoided as much as possible Where neighbours are not annoyed by operation sound or hot air Where rigid wall or support is available to prevent the increase of opera tion sound or vibration Where there is no risk of combustible gas leakage When installing ...

Page 5: ...IRED AROUND OUTDOOR UNIT 500 or more 200 or more 350 or more 100 or more 1 Obstacles above When there is no obstacle in front and on the sides of the unit it is allowed to install the unit where an obstacle is above the unit only if the space shown in the figure is provided 500 or more 100 or more 4 Obstacles in front and behind The unit can be used by at taching an optional outdoor blowing guide ...

Page 6: ...nt C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m M kg Amin m 1 0 12 1 5 ...

Page 7: ...indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling concealed 2 2 m or more There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15 5 4 5 20 5 0 24 5 5 29 6 0 35 6 5 41 7 0 47 7 5 54 Wall mounted h0 1 8 m Ceiling concealed Cassette Ceiling...

Page 8: ...ocket 1 1 Note 1 Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the left table is quantity to be used per indoor unit WARNING To avoid risk of fire embed or protect the refrigerant piping External damage on the refrigerant piping can be cause of fire When the piping is to be attached to a wall containing metals ...

Page 9: ...for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 3 PIPE CONNECTION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Terminal block for powe...

Page 10: ...Die Copper pipe Clutch type Flaring tool Wing nut type Copper pipe 1 Cut the copper pipe correctly with pipe cutter Fig 1 2 2 Completely remove all burrs from the cut cross section of pipe Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not...

Page 11: ...s 10 Leak test Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R32 R410A Gauge manifold valve for R32 R410A Charge hose for R32 R410A Refrigerant gas cylinder for R32 R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Outdoor unit Union Union Union Stop valve for GAS Stop valve cap Torque 21 5 t...

Page 12: ...as a wiring piping correction function which corrects wiring and piping combination When there is possibility of incorrect wiring and piping combi nation and confirming the combination is difficult use this function to detect and correct the combination by following the procedures below Make sure that the following is done Power is supplied to the unit Stop valves are open Note During detection th...

Page 13: ...lation manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 05 MPa Gauge approx 0 5 kgf cm2 or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of the refrigerant in the system an...

Page 14: ...50VF N V Hz kW kW A A 220 50 5 9 230 50 5 6 240 50 5 4 220 50 6 1 230 50 5 8 5 0 1 26 18 0 27 19 C 35 24 C 6 0 1 30 18 0 20 C 7 6 C 240 50 5 6 FUNCTION VOLTAGE FREQUENCY CAPACITY INPUT SET CURRENT MAX CURRENT COOLING HEATING IP24 1 4kg 57kg Manufacturer MITSUBISHI ELECTRIC CONSUMER PRODUCTS THAILAND CO LTD 700 406 MOO 7 TAMBON DON HUA ROH AMPHUR MUANG CHONBURI 20000 THAILAND 0035 RATING CONDITION ...

Page 15: ...и по долу за употреба в жилищни търговски и леки промишлени условия erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer vakuuttaa täten yksinomaisella vastuullaan että jäljempänä kuvatut asuinrakennuksiin pienteollisuuskäyttöön ja kaupalliseen käyttöön tarkoitetut ilmastointilaitteet ja lämpöpumput настоящим зая...

Page 16: ...rezionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travel...

Reviews: