En-5
1-4-2. Minimum installation area for Indoor units
Install in a room with a floor area of Amin or more, corresponding to refrigerant quantity M (factory-charged refri locally added refrigerant).
Install the indoor unit so that the height from the floor to the bottom of the indoor unit is h0;
for wall mounted: 1.8 m or more;
for ceiling suspended, cassette and ceiling concealed: 2.2 m or more.
There are restrictions in installation height for each model, so read the installation manual for the particular unit.
M [kg]
Amin [m²]
1.0
3
1.5
4.5
2.0
6
2.5
7.5
3.0
9
3.5
12
4.0
15.5
4.5
20
5.0
24
5.5
29
6.0
35
6.5
41
7.0
47
7.5
54
Wall mounted
h0
]
1.8 [m]
Ceiling concealed
Cassette
Ceiling suspended
h0
]
2.2 [m]
h0
]
2.2 [m]
h0
]
2.2 [m]