4-4. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT)

4-5. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT

•  Description of the function:

  With this function, once the operation mode is locked to either COOL/DRY mode 

or HEAT mode, the air conditioner operates in that mode only.

*  Changing the setting is required to activate this function. Please explain about 

this function to your customers and ask them whether they want to use it.

[How to lock the operation mode]

1) Be sure to turn off the main power for the air conditioner before making the 

setting.

2) Set the “3” of SW1 on the outdoor controller board to ON to enable this function.

3) To lock the operation mode in COOL/DRY mode, set the “4” of SW1 on the 

outdoor controller board to OFF. To lock the operation in HEAT mode, set the 

same switch to ON.

4) Turn on the main power for the air conditioner.

•  Description of the function:

  With this function, the operating noise of the outdoor unit can be lowered by reducing the operation load, for example, during nighttime in COOL mode. 

However, please note that the cooling and heating capacity may lower if this function is activated.

*  Changing the setting is required to activate this function. Please explain about this function to your customers and ask them whether they want to use it.

Lower the operating noise

[How to lower the operating noise]

1) Be sure to turn off the main power for the air conditioner before making the setting.

2) Set the “5” of SW1 on the outdoor controller board to ON to enable this function.

3) Turn on the main power for the air conditioner.

HEAT

COOL/DRY

LED

SW1

SW871

SW2

SW1

ON

1   2   3   4   5   6

SW1

ON

1   2   3   4   5   6

4-6. TEST RUN

•  Test runs of the indoor units should be performed individually. See the installation manual coming with the indoor unit, and make sure all the units operate 

properly.

•  If the test run with all the units is performed at once, possible erroneous connections of the refrigerant pipes and the indoor/outdoor unit connecting wires 

cannot be detected. Thus, be sure to perform the test run one by one.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner. 

Wiring/piping correction function

This unit has a wiring/piping correction function which corrects wiring and piping combination. When there is possibility of incorrect wiring and piping combi

-

nation, and confirming the combination is difficult, use this function to detect and correct the combination by following the procedures below.
Make sure that the following is done.

•  Power is supplied to the unit.

•  Stop valves are open.

Note:

During detection, the operation of the indoor unit is controlled by the outdoor unit. During detection, the indoor unit automatically stops operation. This is not 

a malfunction.
Procedure

Press the piping/wiring correction switch (SW871) 1 minute or more after turning on the 

power supply.
•  Correction completes in 10 to 15 minutes. When the correction is completed, its result 

is shown by LED indication. Details are described in the following table.

•  To cancel this function during its operation, press the piping/wiring correction switch 

(SW871) again.

•  When the correction completed without error, do not press the piping/wiring correction 

switch (SW871) again.

When the result is “Not completed”, press the piping/wiring correction switch (SW871) again 

to cancel this function. Then, confirm the wiring and piping combination in a conventional 

manner by operating the indoor units one by one.
•  The operation is done while the power is supplied. Make sure not to contact parts other 

than the switch, including the P.C. board. This may cause electric shock or burn by hot 

parts and live parts around the switch. Contacting the live parts may cause P.C. board 

damage.

•  To prevent electronic control P.C. board damage, make sure to perform static elimination 

before operating this function.

•  This function does not operate when the outside temperature is 0°C or below.

LED indication during detection:

LED1

(Red)

LED2

(Yellow)

LED3 

(Green)

Lit

Lit

Once

Result of piping/wiring correction function

LED1

(Red)

LED2

(Yellow)

LED3

(Green)

Result

Lit

Not lit

Lit

Completed

(Problem corrected or 

normal)

Once

Once

Once

Not completed 

(Detection failed)

Other indications

Refer to “SAFETY PRE

-

CAUTIONS WHEN LED 

BLINKS” located behind 

the top panel.

4-7. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, 

how to remove or put the remote controller in the remote controller holder, how to clean, precautions for operation, etc.).

•  Recommend the user to read the OPERATING INSTRUCTIONS carefully.

VG79A985H01_01En.indd   10

2018/10/03   11:45:08

Summary of Contents for MXZ-3HA50VF

Page 1: ...ão Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidade interior consulte o manual de instalação da unidade interior Installationshåndbog Til INSTALLATØREN Denne håndbog beskriver kun hvordan udendørsenheden installeres Vedrørende installation af indendørsenheden henvises til installationshåndbogen for indendørsenheden Installations...

Page 2: ...і а потім мову BG Посетете горепосочения уебсайт за да изтеглите ръководства като изберете име на модел и след това език PL Odwiedź powyższą stronę internetową aby pobrać instrukcje wybierz nazwę modelu a następnie język CS Příručky naleznete ke stažení na internetové stránce zmíněné výše poté co zvolíte model a jazyk SK Na webovej stránke vyššie si môžete stiahnuť návody Vyberte názov modelu a zv...

Page 3: ...ation ventilate the room Check that the refrigerant does not leak after installation has been completed If refrigerant leaks and comes in contact with fire or heating part of such a fan heater kerosene heater or cooking stove it will create harmful gas Provide ventilation in accordance with EN378 1 Check that the refrigerant gas does not leak after installation has been completed If refrigerant ga...

Page 4: ...LECTING THE INSTALLATION LOCATION Where it is not exposed to strong wind Where airflow is good and dustless Where rain or direct sunshine can be avoided as much as possible Where neighbours are not annoyed by operation sound or hot air Where rigid wall or support is available to prevent the increase of opera tion sound or vibration Where there is no risk of combustible gas leakage When installing ...

Page 5: ...IRED AROUND OUTDOOR UNIT 500 or more 200 or more 350 or more 100 or more 1 Obstacles above When there is no obstacle in front and on the sides of the unit it is allowed to install the unit where an obstacle is above the unit only if the space shown in the figure is provided 500 or more 100 or more 4 Obstacles in front and behind The unit can be used by at taching an optional outdoor blowing guide ...

Page 6: ...nt C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m M kg Amin m 1 0 12 1 5 ...

Page 7: ...indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling concealed 2 2 m or more There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15 5 4 5 20 5 0 24 5 5 29 6 0 35 6 5 41 7 0 47 7 5 54 Wall mounted h0 1 8 m Ceiling concealed Cassette Ceiling...

Page 8: ...ocket 1 1 Note 1 Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the left table is quantity to be used per indoor unit WARNING To avoid risk of fire embed or protect the refrigerant piping External damage on the refrigerant piping can be cause of fire When the piping is to be attached to a wall containing metals ...

Page 9: ...for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 3 PIPE CONNECTION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Terminal block for powe...

Page 10: ...Die Copper pipe Clutch type Flaring tool Wing nut type Copper pipe 1 Cut the copper pipe correctly with pipe cutter Fig 1 2 2 Completely remove all burrs from the cut cross section of pipe Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not...

Page 11: ...s 10 Leak test Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R32 R410A Gauge manifold valve for R32 R410A Charge hose for R32 R410A Refrigerant gas cylinder for R32 R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Outdoor unit Union Union Union Stop valve for GAS Stop valve cap Torque 21 5 t...

Page 12: ...as a wiring piping correction function which corrects wiring and piping combination When there is possibility of incorrect wiring and piping combi nation and confirming the combination is difficult use this function to detect and correct the combination by following the procedures below Make sure that the following is done Power is supplied to the unit Stop valves are open Note During detection th...

Page 13: ...lation manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 05 MPa Gauge approx 0 5 kgf cm2 or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of the refrigerant in the system an...

Page 14: ...50VF N V Hz kW kW A A 220 50 5 9 230 50 5 6 240 50 5 4 220 50 6 1 230 50 5 8 5 0 1 26 18 0 27 19 C 35 24 C 6 0 1 30 18 0 20 C 7 6 C 240 50 5 6 FUNCTION VOLTAGE FREQUENCY CAPACITY INPUT SET CURRENT MAX CURRENT COOLING HEATING IP24 1 4kg 57kg Manufacturer MITSUBISHI ELECTRIC CONSUMER PRODUCTS THAILAND CO LTD 700 406 MOO 7 TAMBON DON HUA ROH AMPHUR MUANG CHONBURI 20000 THAILAND 0035 RATING CONDITION ...

Page 15: ...и по долу за употреба в жилищни търговски и леки промишлени условия erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer vakuuttaa täten yksinomaisella vastuullaan että jäljempänä kuvatut asuinrakennuksiin pienteollisuuskäyttöön ja kaupalliseen käyttöön tarkoitetut ilmastointilaitteet ja lämpöpumput настоящим зая...

Page 16: ...rezionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travel...

Reviews: