background image

En-9

4-1. PURGING PROCEDURES AND LEAK TEST

4-2. GAS CHARGE

Perform gas charge to unit.

1) Connect gas cylinder to the service port of stop valve.

2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air conditioner 

for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrigerat

-

ing cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use 

liquid refrigerant. Charge the liquid refrigerant slowly, otherwise the compressor 

will be locked.

To  maintain  the  high  pressure  of  the  gas  cylinder,  warm  the  gas  cylinder  with 

warm water (under 40°C) during cold season. But never use naked fire or steam.

1) Remove service port cap of stop valve on the side of the outdoor unit 

gas pipe. (The stop valves are fully closed and covered in caps in 

their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of 

stop valve on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)

4) Check the vacuum with gauge manifold valve, then close gauge 

manifold valve, and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge 

manifold valve remains in the same position. Confirm that pressure 

gauge shows -0.101 MPa [Gauge] (-760 mmHg).

6) Remove gauge manifold valve quickly from service port of stop 

valve.

7) Fully open all stop valves on the gas pipe and the liquid pipe. Oper

-

ating without fully opening lowers the performance and this causes 

trouble.

8) Refer to 1-2., and charge the prescribed amount of refrigerant if 

needed. Be sure to charge slowly with liquid refrigerant. 

9) Tighten cap of service port to obtain the initial status.

10) Leak test

Union

Stop valve

Liquid 

pipe

Indoor 

unit

Stop valve with 

service port

Gas 

pipe

Refrigerant gas 

cylinder operating 

valve

(for R32, R410A)

Gauge manifold 

valve (for R32, 

R410A)

Charge hose 

(for R32, 

R410A)

Refrigerant gas cylinder for R32, R410A 

with siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

Union

Union
Union

Stop valve 

for GAS

Stop valve cap

(Torque 21.5 to 

27.5 N•m, 220 

to 280 kgf•cm)

Gauge manifold 

valve (for R32, 

R410A)

Compound pressure 

gauge (for R32, R410A)

–0.101MPa  

(–760 mmHg)

Handle 

Low

Handle High

Vacuum pump

(for R32, R410A)

*Close

*Open

Hexagonal wrench

*4 to 5 turns

Stop valve 

for LIQUID

Pressure gauge

(for R32, R410A)

Precautions when using the control 

valve

When attaching the control valve 

to the service port, valve core may 

deform or loosen if excess pres

-

sure is applied. This may cause 

gas leak.

Service port

Charge hose 

(for R32, 

R410A)

Body

Close

Open

Control 

valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then tighten part A. Do not tighten 

part A or turn the body when valve 

core is in open position.

Service port cap

(Torque 13.7 to 

17.7 N•m, 140 to 

180 kgf•cm)

Charge hose (for 

R32, R410A)

4-3. REMOVING THE MAINTENANCE PANEL

The setting of Dip Switch on the outdoor controller board can be changed 

without removing the front panel.

Follow the procedures below to remove the maintenance panel and set 

the Dip Switch.

1) Remove screw(s) which fix the maintenance panel.

2) Remove the maintenance panel, and perform necessary settings.

3) Install the maintenance panel.

Note:

Make sure to fix the maintenance panel securely. Incomplete installation 

could cause malfunction.

Maintenance panel

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

 WARNING

To avoid risk of fire, make sure that there are no flammable 

hazards or ignition risks before opening the stop valves.

Make sure to replace the cap after 

the operation.

<R32>

VG79A985H01_01En.indd   9

2018/10/03   11:45:08

Summary of Contents for MXZ-3HA50VF

Page 1: ...ão Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalação da unidade interior consulte o manual de instalação da unidade interior Installationshåndbog Til INSTALLATØREN Denne håndbog beskriver kun hvordan udendørsenheden installeres Vedrørende installation af indendørsenheden henvises til installationshåndbogen for indendørsenheden Installations...

Page 2: ...і а потім мову BG Посетете горепосочения уебсайт за да изтеглите ръководства като изберете име на модел и след това език PL Odwiedź powyższą stronę internetową aby pobrać instrukcje wybierz nazwę modelu a następnie język CS Příručky naleznete ke stažení na internetové stránce zmíněné výše poté co zvolíte model a jazyk SK Na webovej stránke vyššie si môžete stiahnuť návody Vyberte názov modelu a zv...

Page 3: ...ation ventilate the room Check that the refrigerant does not leak after installation has been completed If refrigerant leaks and comes in contact with fire or heating part of such a fan heater kerosene heater or cooking stove it will create harmful gas Provide ventilation in accordance with EN378 1 Check that the refrigerant gas does not leak after installation has been completed If refrigerant ga...

Page 4: ...LECTING THE INSTALLATION LOCATION Where it is not exposed to strong wind Where airflow is good and dustless Where rain or direct sunshine can be avoided as much as possible Where neighbours are not annoyed by operation sound or hot air Where rigid wall or support is available to prevent the increase of opera tion sound or vibration Where there is no risk of combustible gas leakage When installing ...

Page 5: ...IRED AROUND OUTDOOR UNIT 500 or more 200 or more 350 or more 100 or more 1 Obstacles above When there is no obstacle in front and on the sides of the unit it is allowed to install the unit where an obstacle is above the unit only if the space shown in the figure is provided 500 or more 100 or more 4 Obstacles in front and behind The unit can be used by at taching an optional outdoor blowing guide ...

Page 6: ...nt C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m M kg Amin m 1 0 12 1 5 ...

Page 7: ...indoor unit is h0 for wall mounted 1 8 m or more for ceiling suspended cassette and ceiling concealed 2 2 m or more There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15 5 4 5 20 5 0 24 5 5 29 6 0 35 6 5 41 7 0 47 7 5 54 Wall mounted h0 1 8 m Ceiling concealed Cassette Ceiling...

Page 8: ...ocket 1 1 Note 1 Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the left table is quantity to be used per indoor unit WARNING To avoid risk of fire embed or protect the refrigerant piping External damage on the refrigerant piping can be cause of fire When the piping is to be attached to a wall containing metals ...

Page 9: ...for each indoor unit 5 Connect power supply cord A 6 Fix indoor outdoor unit connecting wire B and power supply cord A with the cable clamps 7 Close the service panel securely Make sure that 3 3 PIPE CONNECTION is completed After making connections between both power supply cord A and indoor outdoor unit connecting wire B be sure to fix both cable and wire with cable clamps Terminal block for powe...

Page 10: ...Die Copper pipe Clutch type Flaring tool Wing nut type Copper pipe 1 Cut the copper pipe correctly with pipe cutter Fig 1 2 2 Completely remove all burrs from the cut cross section of pipe Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not...

Page 11: ...s 10 Leak test Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R32 R410A Gauge manifold valve for R32 R410A Charge hose for R32 R410A Refrigerant gas cylinder for R32 R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Outdoor unit Union Union Union Stop valve for GAS Stop valve cap Torque 21 5 t...

Page 12: ...as a wiring piping correction function which corrects wiring and piping combination When there is possibility of incorrect wiring and piping combi nation and confirming the combination is difficult use this function to detect and correct the combination by following the procedures below Make sure that the following is done Power is supplied to the unit Stop valves are open Note During detection th...

Page 13: ...lation manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 05 MPa Gauge approx 0 5 kgf cm2 or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of the refrigerant in the system an...

Page 14: ...50VF N V Hz kW kW A A 220 50 5 9 230 50 5 6 240 50 5 4 220 50 6 1 230 50 5 8 5 0 1 26 18 0 27 19 C 35 24 C 6 0 1 30 18 0 20 C 7 6 C 240 50 5 6 FUNCTION VOLTAGE FREQUENCY CAPACITY INPUT SET CURRENT MAX CURRENT COOLING HEATING IP24 1 4kg 57kg Manufacturer MITSUBISHI ELECTRIC CONSUMER PRODUCTS THAILAND CO LTD 700 406 MOO 7 TAMBON DON HUA ROH AMPHUR MUANG CHONBURI 20000 THAILAND 0035 RATING CONDITION ...

Page 15: ...и по долу за употреба в жилищни търговски и леки промишлени условия erklærer et fullstendig ansvar for undernevnte klimaanlegg og varmepumper ved bruk i boliger samt kommersielle og lettindustrielle miljøer vakuuttaa täten yksinomaisella vastuullaan että jäljempänä kuvatut asuinrakennuksiin pienteollisuuskäyttöön ja kaupalliseen käyttöön tarkoitetut ilmastointilaitteet ja lämpöpumput настоящим зая...

Page 16: ...rezionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travel...

Reviews: