1-4. SELECTING THE INSTALLATION LOCATION

•  Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where rain or direct sunshine can be avoided as much as possible.

•  Where neighbours are not annoyed by operation sound or hot air.

•  Where rigid wall or support is available to prevent the increase of operation 

sound or vibration.

•  Where there is no risk of combustible gas leakage.

•  When installing the unit, be sure to secure the unit legs.

•  Where it is at least 10 ft. (3 m) away from the antenna of TV set or radio. Op

-

eration of the air conditioner may interfere with radio or TV reception in areas 

where reception is weak. An amplifier may be required for the affected device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or blowing snow. In areas 

with heavy snow, please  install  a canopy, a pedestal  and/or some baffle 

boards.

Note:

It is advisable to make a piping loop near outdoor unit so as to reduce vibration 

transmitted from there.

Note: 

When operating the air conditioner in low outside temperature, be sure to 

follow the instructions described below.

•  Never install the outdoor unit in a place where its air inlet/outlet side may 

be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet side 

facing the wall.

•  To prevent exposure to wind, it is recommended to install a baffle board on 

the air outlet side of the outdoor unit.

Avoid  the  following  places  for  installation  where  air  conditioner  trouble  is 

liable to occur.

•  Where flammable gas could leak.

•  Where there is much machine oil.

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as a hot spring.

•  Where there is high-frequency or wireless equipment.

•  Where there is emission of high levels of VOCs, including phthalate com

-

pounds, formaldehyde, etc., which may cause chemical cracking.

3. 

Obstacles in front (blowing) only

When there is an obstacle in front of the unit as shown in the figure, open 

space above, behind, and on the sides of the unit is required.

2. 

Front (blowing) side open

As long as space indicated in the figure is provided, it is allowed to install the 

unit where obstacles are behind and on the sides of the unit. (No obstacle 

above the unit)

FREE SPACE REQUIRED AROUND OUTDOOR UNIT

Service space

•  When installing the unit in an area that is enclosed with walls such as a 

verandah, be sure to have enough space as shown below. 

  In this case, the air conditioning capacity and power consumption might 

deteriorate.

•  When installing two or more units, do not install the units in front or behind 

each other.

1. 

Obstacles above

When there is no obstacle in front and on the sides of the unit, it is allowed 

to install the unit where an obstacle is above the unit only if the space shown 

in the figure is provided.

6. 

Service space

Provide space for service and maintenance as shown in the figure.

19-11/16 (500) or more

3-15/16 (100) or more

5. 

Obstacles in front, behind and on side(s)

(Unit: inch (mm))

Height of the obstacle is 47-1/4 (1200) or less

19-11/16 (500) or more

3-15/16 (100) or more

19-11/16 (500) 

or more

13-25/32 (350) or more

3-15/16 (100) or more

13-25/32 (350) or more

3-15/16 (100) or more

7-7/8 (200) or more

13-25/32 (350) or more

3-15/16 (100) 

or more

7-7/8 (200) or more

13-25/32 (350) 

or more

19-11/16 (500) 

or more

19-11/16 (500) 

or more

4. 

Obstacles in front and behind

The unit can be used by attaching an optional outdoor blowing guide 

(PAC-SH96SG-E) (but both sides and top are open).

3-15/16 (100) or more

Blowing guide (PAC-SH96SG-E)

19-11/16 (500) or more

1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS

If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.

Port size of outdoor unit

Optional different-diameter joints (port size of outdoor unit →

 diameter of connection pipe)

MXZ-3C

MXZ-4C

Liquid / Gas

1/4 (6.35) → 3/8 (9.52) : PAC-493PI

3/8 (9.52) → 1/2 (12.7) : MAC-454JP-E

3/8 (9.52) → 5/8 (15.88) : PAC-SG76RJ-E

1/2 (12.7) → 3/8 (9.52) : MAC-A455JP-E

1/2 (12.7) → 5/8 (15.88) : MAC-A456JP-E

Refer to the installation manual of indoor unit for the diameter of connection pipe of indoor unit.

A UNIT

1/4 (6.35) / 1/2 (12.7)

B - C UNIT B - D UNIT

1/4 (6.35) / 3/8 (9.52)

(Unit: inch (mm))

WG79A686H01_en.indd   2

11/24/2015   9:04:54 AM

Summary of Contents for MXZ-3C30NA2

Page 1: ...ATEUR Cette notice ne décrit que l installation de l appareil extérieur Lors de l installation de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local Manual de instalación Para el INSTALADOR En este manual sólo se describe la instalación de la unidad exterior Pa...

Page 2: ...ssure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could cause the pipes to burst or injury n When pumping down the refrigerant stop the compressor before discon necting the refrigerant pipes If the refrigerant pipes are disconnected while the compressor is running and the stop valve is open air could be drawn in and the pressure in the r...

Page 3: ...the sides of the unit is required 2 Front blowing side open As long as space indicated in the figure is provided it is allowed to install the unit where obstacles are behind and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough space as s...

Page 4: ...w for I 2 to 7 K Wall hole sleeve 1 L Soft PVC hose 19 32 in 15 mm inner diameter or hard PVC pipe VP16 for drain socket 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 3 ft 1 m away from the TV antenna wire The Q ty for B to K in the above table is quantity to be used per indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 500 mm if t...

Page 5: ...8 Connect power supply cord A 9 Close the service panel securely Make sure that 3 2 PIPE CONNEC TION is completed Connecting order Connect the terminal block in following order A B C D P CONNECTING WIRES AND CONNECTING GROUND WIRE Use solid conductor Min AWG14 or stranded conductor Min AWG14 Use double insulated copper wire with 600 V insulation Use copper conductors only Follow local electrical c...

Page 6: ...gas pipe The stop valves are fully closed and covered in caps in their initial state 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outdoor unit 3 Run the vacuum pump Vacuumize for more than 15 minutes 4 Check the vacuum with gauge manifold valve then close gauge manifold valve and stop the vacuum pump 5 Leave as it is for one or two minute...

Page 7: ...NIT COOL DRY HEAT Description of the function With this function once the operation mode is locked to either COOL DRY mode or HEAT mode the air conditioner operates in that mode only Changing the setting is required to activate this function Please explain about this function to your customers and ask them whether they want to use it How to lock the operation mode 1 Be sure to turn off the main po...

Page 8: ...hen the correction completed without error do not press the piping wiring correction switch SW871 again When the result is Not completed press the piping wiring correction switch SW871 again to cancel this function Then confirm the wiring and piping combination in a conventional manner by operating the indoor units one by one The operation is done while the power is supplied Make sure not to conta...

Page 9: ...z pas le réfrigérant dans l atmosphère En cas de fuite de réfrigérant pendant l installation aérez la pièce Tout contact entre le réfrigérant et une flamme pourrait provoquer l émission de gaz toxiques Des fuites de réfrigérant peuvent provoquer une asphyxie Aérez la pièce n A la fin de l installation aucune fuite de réfrigérant ne doit être présente sur le circuit En cas de fuite de réfrigérant d...

Page 10: ...e est basse veillez à observer les instructions ci dessous N installez jamais l unité externe dans un endroit où le côté présentant l entrée la sortie d air risque d être directement exposé au vent Pour protéger l unité externe du vent installez la de façon à ce que l entrée d air soit face au mur Pour éviter toute exposition au vent il est recommandé d installer un écran de protection du côté de ...

Page 11: ...ie doit être fixée sur un mur contenant des métaux de l étain p ex ou un treillis métallique utiliser un morceau de bois traité d une épais seur de 25 32 po 20 mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vinyle Pour utiliser la tuyauterie existante effectuer un cycle COOL REFROI DISSEMENT de 30 minutes et lancer l aspiration ...

Page 12: ...électrique local CÂBLE D ALIMENTATION ÉLECTRIQUE ET CÂBLE DE MISE À LA TERRE Utiliser un conducteur massif ou toronné min AWG12 Utiliser des conducteurs en cuivre uniquement Respecter le code électrique local AVERTISSEMENT Utiliser le câble de connexion conforme aux normes techniques pour raccorder les unités interne et externe et fixer le câble fermement sur la bloc de sortie de façon que le côté...

Page 13: ...Serrez le bouchon de l ouverture de service pour recréer les conditions d origine 10 Test de contrôle des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile réfrigérante G sur les embouts évasés des tuyaux ainsi que sur les raccords de tuyau de l appareil extérieur 2 Alignez la partie médiane du tuyau sur les raccords de tuyau de l appareil extérieur et serrez les écrous évasés...

Page 14: ... DE FONCTIONNEMENT DE L APPAREIL EXTÉRIEUR REFROIDISSEMENT DÉSHUMIDIFICATION CHAUFFAGE Description de la fonction Lorsque cette fonction est sélectionnée si le mode de fonctionnement est blo qué sur COOL DRY REFROIDISSEMENT DÉSHUMIDIFICATION ou HEAT CHAUFFAGE le climatiseur fonctionne uniquement dans ce mode Il est nécessaire de modifie la configration pour pouvoir sélectionner cette fonction Prés...

Page 15: ...en marche trop rapide Lorsque le compresseur s arrête le dispositif de protection contre la remise en marche à trop brève échéance s enclenche Le compresseur restera arrêté trois minutes avant de se remettre en marche afin de protéger le climatiseur Fonction de correction de câblage tuyauterie L appareil est équipé d une fonction qui permet de corriger les branchements de câblage et de tuyauterie ...

Page 16: ... sistema ocasionará fallos mecánicos malfuncionamiento del sistema o averías en la unidad En el peor de los casos esto podría llegar a ser un serio impedimento para garantizar el uso seguro del producto n No descargue el refrigerante en el ambiente Si se producen fugas de refrige rante durante la instalación ventile la habitación Si el refrigerante entra en contacto con una llama podría generarse ...

Page 17: ...xterior sea baja observe las instrucciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entra da salida de aire quede expuesto directamente al viento Para evitar la exposición al viento instale la unidad exterior con el lado de entrada de aire hacia la pared Para evitar la exposición al viento se recomienda instalar una placa de flectora en el lado de salida de a...

Page 18: ... si la parte delantera y ambos lados están abiertos Después de la prueba de fugas aplique material aislante de modo que no queden huecos Cuando los tubos deban instalarse en una pared con contenido metálico placas de latón o rejillas metálicas ponga un trozo de madera tratada químicamente de 25 32 pulg 20 mm o más de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8 vueltas de cinta...

Page 19: ... de 600 V Use únicamente conductores de cobre Siga la normativa eléctrica local CABLE DE ALIMENTACIÓN Y CABLE DE TIERRA Utilice un conductor sólido o trenzado con un calibre mín AWG12 Use únicamente conductores de cobre Siga la normativa eléctrica local ATENCIÓN Conecte las unidades interior y exterior con el cable de conexión normalizado destinado a este fin y sujete bien el cable al panel de ter...

Page 20: ... la tapa de la abertura de servicio de la válvula de retención situada en el lado de la tubería de gas de la unidad exterior Inicialmente las válvulas de retención están completamente cerradas y cubiertas con sus tapas 2 Conecte la válvula colectora de manómetro y la bomba de vacío al puerto de servicio de la válvula de retención en el lado de la tubería del gas de la unidad exterior 3 Ponga en fu...

Page 21: ...IÓN 4 4 REDUCIR EL RUIDO DE FUNCIONAMIENTO DE LA UNIDAD EXTERIOR Descripción de la función Con esta función una vez que el modo de funcionamiento se ha bloqueado en COOL DRY REFRIGERACIÓN DESHUMIDIFICACIÓN o HEAT CALEFAC CIÓN el acondicionador de aire funciona únicamente en ese modo Es necesario cambiar el ajuste para activar esta función Explique esta function a sus clientes y pregúnteles si dese...

Page 22: ...ba de funcionamiento de las unidades una a una Acerca del mecanismo de protección de la reanudación Una vez se haya detenido el compresor el dispositivo de prevención de la reanudación se activa de forma que el compresor no vuelve a ponerse en funcionamiento durante 3 minutos para proteger el acondicionador de aire Función de corrección de conexiones tuberías Esta unidad tiene una función de corre...

Page 23: ......

Page 24: ...HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN WG79A686H01 ...

Reviews: