39
Check of LEV
No
Yes
Yes
No
Turn ON the breaker to the outdoor unit after checking LEV
coil is mounted to the LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of LEV coil with your hand?
Disconnect the connectors.
MXZ-2HJ40VA
CN724: LEV A, CN725: LEV B
MXZ-3HJ50VA
CN791: LEV A, CN792: LEV B,
CN793: LEV C, CN795: LEV E
Normal
Is the resistance of the LEV coil normal?
(Refer to 11-5.)
Replace the inverter P.C. board or
the outdoor control P.C. board.
Replace LEV coil.
• In cooling, the heat exchanger of non-operating indoor unit has frosted.
• In heating, non-operating indoor unit gets warm.
MXZ-2HJ40VA
MXZ-3HJ50VA
CN724
CN725
Inverter P.C. board
Outdoor control
P.C. board
CN791
CN792
CN793
CN795
―