Outdoor model
MXZ-3HJ50VA
Outdoor unit power supply
Single phase
230 V, 50 Hz
System
Indoor units number
2 to 3
Piping total length
m
Max. 50
Connecting pipe length
m
Max. 25
Height difference (Indoor ~ Outdoor)
m
Refer to 7 REFRIGERANT SYSTEM DIAGRAM.
Height difference (Indoor ~ Indoor)
m
Refer to 7 REFRIGERANT SYSTEM DIAGRAM.
Function
Cooling
Heating
Capacity Rated frequency (Min.-Max.) 2
kW
5.0 (2.7 - 6.5)
6.0 (2.4 - 7.5)
Breaker capacity
A
25
Electrical
data
Power input (Total) 1, 2
W
1,130
1,310
Running current (Total) 1, 2
A
5.0
5.8
Power factor (Total) 1, 2
%
99
Starting current (Total) 1, 2
A
5.8
Coef
fi
cient of performance (C.O.P) (Total) 1, 2
4.42
4.58
Compressor
Model
SNB130FGBH1T
Output
W
1,300
Current 1, 2
A
4.5
5.3
Refrigeration oil (Model)
L
0.7 (NEO22)
Fan
motor
Model
SIC-71FW-F764-1
Current 1, 2
A
0.20
0.23
Dimensions W x H x D
mm
840 x 710 x 330
Weight
kg
57
Special
remarks
Air
fl
ow (Rated)
m
3
/h
2,252
2,379
Sound level (Rated)
dB(A)
50
53
Fan speed (Rated)
rpm
630
660
Refrigerant
fi
lling capacity (R410A)
kg
2.7
1 Measured under rated operating frequency.
2 When connected with below indoor units.
MSZ- MSZ- MSZ-HJ25VA
NOTE:
Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
COOLING INDOOR
Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C
OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C
HEATING INDOOR Dry-bulb temperature 20.0 °C
OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature 6.0 °C
OBH709A