11-4. TROUBLESHOOTING CHECK TABLE
MXZ-2HJ
No.
1
2
3
4
5
6
9
10
11
12
13
14
15
16
Symptom
'Outdoor
unit stops
and restarts
3 minutes
later' is
repeated.
Primary current protection
Secondary current protection
High-pressure protection
Defrosting in cooling
3 times
Lighted
Discharge temperature
protection
4 times
Lighted
Low discharge
temperature protection
Check the refrigerant circuit and the refrigerant amount.
Refer to 11-6. "Check of LEV".
Refer to 11-6.
"Check of outdoor thermistors".
Refer to 11-6.
"Check of LEV".
Check the refrigerant circuit and the refrigerant amount.
These symptoms do not mean any abnormality of the
product, but check the following points.
Check if indoor filters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circulation is short cycled.
Twice
Lighted
Once
Lighted
The discharge temperature exceeds 100°C during operation.
The frequency of the compressor is kept 80 Hz or more and the discharge
temperature is kept under 50°C (COOL mode)/40°C (HEAT mode) for
more than 40 minutes.
The input current exceeds 10 A.
The current of the compressor exceeds 17 A.
The indoor gas pipe temperature exceeds 45°C during heating.
The indoor gas pipe temperature falls 3°C or below during cooling.
Outdoor unit
operates.
17
18
19
20
7
8
LED1(Red) LED2(Yellow)
Lighted
Twice
Outdoor power system
Lighted
3 times
Discharge temperature
thermistor
Outdoor heat exchanger
temperature thermistor
Defrost thermistor
Lighted
7 times
Nonvolatile memory data
Replace the inverter P.C. board.
Abnormal point / Condition
Remedy
A short circuit is detected in the thermistor during operation, or when
an open circuit is detected in the thermistor after 5 minutes (in cooling)
and 10 minutes (in heating) of compressor start-up.
A short circuit is detected in the thermistor during operation, or when an
open circuit is detected in the thermistor after 5 minutes of compressor
start-up.
A closed valve and air trapped in the refrigerant circuit are detected
based on the temperature sensed by the indoor and outdoor thermistors
and the current of the compressor.
Replace the inverter P.C. board.
Indication
Overcurrent protection cut-out operates 3 consecutive times
within 1 minute after the compressor gets started.
A short circuit is detected in the thermistor during operation, or when an
open circuit is detected in the thermistor after 10 minutes of compressor
start-up.
Condition
The nonvolatile memory data cannot be read properly.
Fin temperature
thermistor
P.C board temperature
thermistor
Lighted
4 times
Ambient temperature
thermistor
A short or open circuit is detected in the thermistor during operation.
A short or open circuit is detected in the thermistor during operation.
5 times
Lighted
Overcurrent
3 times
Not lighted
Discharge temperature
protection
Fin temperature
protection
P.C. board temperature
protection
High-pressure
protection
Replace the inverter P.C. board.
Bus-bar voltage
protection
Not lighted
Outdoor fan motor
8 times
Not lighted
Current sensor
protection
Replace the inverter P.C. board.
Not lighted
Compressor
Refer to 11-6. "Check of outdoor fan motor".
Reconnect compressor connector.
Refer to 11-6.
"How to check inverter/compressor".
Check the stop valve.
Check the amount of gas and the refrigerant circuit.
Check the stop valve.
Check the amount of gas and the refrigerant circuit.
Refer to 11-6. "Check of LEV".
&KHFNWKHUHIULJHUDQWFLUFXLWDQGWKHUHIULJHUDQWDPRXQW
5HIHUWR
"Check of outdoor fan motor".
Reconnect compressor connector.
Refer to 11-6. "How to check inverter/compressor".
Check the stop valve.
&KHFNIRUDJDVOHDNLQDFRQQHFWLQJSLSLQJHWF
&KHFNWKHVWRSYDOYH
5HIHUWR
"Check of outdoor refrigerant circuit".
Twice
Not lighted
4 times
Not lighted
5 times
Not lighted
9 times
Not lighted
18 A current flows into intelligent power module.
The bus-bar voltage exceeds 430 V or falls to 50 V or below during
compressor operating.
Discharge temperature exceeds 116°C during operation. Compressor can
restart if discharge temperature thermistor reads 100°C or less 3 minutes
later.
The fin temperature exceeds 90°C during operation.
The P.C. board temperature exceeds 78°C during operation.
Failure occurs 3 consecutive times within 30 seconds after the fan
gets started.
A short or open circuit is detected in the current sensor during
compressor operating.
The compressor does not synchronize with the operating power.
The outdoor heat exchanger temperature exceeds 70°C during cooling
or indoor gas pipe temperature exceeds 70°C during heating.
Outdoor unit
does not
operate.
Lighted
Once
LEV and drain pump
Check the connection of the compressor connecting
wire.
Refer to 11-6. "How to check inverter/compressor".
Check the stop valve.
Refer to 11-6. "Check of outdoor thermistors".
Refer to 11-6. "Check of outdoor thermistors".
Refer to 11-6. "Check of outdoor thermistors".
Refer to 11-6. "Check of LEV".
Check the drain pump of the indoor unit.
The indoor unit detects an abnormality in the LEV and drain pump.
Lighted
11 times
Lighted
17 times
Stop valve
Closed valve
Outdoor refrigerant
system abnormality
Closed valve is detected by compressor current.
Check the stop valve.
13 times
10 times
OBH709A