4-1. PURGING PROCEDURES AND LEA  TEST

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. 

(The stop valves are fully closed and covered in caps in their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve 

on the side of the outdoor unit gas pipe.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)

4) Chec  the vacuum  ith gauge manifold valve, then close gauge manifold 

valve, and stop the vacuum pump.

5) Leave as it is for one or t o minutes. Ma e sure the pointer of gauge manifold 

valve remains in the same position. Confirm that pressure gauge sho s -14.7 

psi [Gauge] (-0.101 MPa).

6) Remove gauge manifold valve quic ly from service port of stop valve.

7) After refrigerant pipes are connected and evacuated, fully open the valve stem 

of all stop valves on both sides of gas pipe and liquid pipe by the hexagonal 

rench. If the valve stem hits the stopper, do not turn it any further. Operating 

w ithout fully opening low ers the performance and this causes trouble.

8) Refer to 1-2., and charge the prescribed amount of refrigerant if needed. Be 

sure to charge slow ly w ith liquid refrigerant. Otherw ise, composition of the 
refrigerant in the system may be changed and affect performance of the air 
conditioner.

9) Tighten cap of service port to obtain the initial status.

10) Leak test

4-2. GAS CHARGE

Perform gas charge to unit.

1) Connect gas cylinder to the service port of stop valve.

2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant,  hile operating the air conditioner for cooling.

N o t e :

In case of adding refrigerant, comply  ith the quantity specified for the refrigerating cycle.

C A U T I O N :

When charging the refrigerant system w ith additional refrigerant, be sure to use liquid refrigerant. 
Adding gas refrigerant may change the composition of the refrigerant in the system and affect 
normal operation of the air conditioner. Also, charge the liquid refrigerant slow ly, otherw ise the 
compressor w ill be locked.
To maintain the high pressure of the gas cylinder, w arm the gas cylinder w ith w arm w ater (under 

104  (40 C)) during cold season. But never use na ed fire or steam.

Union

Stop valve

Liquid 
pipe

Indoor 

unit

Stop valve  ith 

service port

Gas 
pipe

Refrigerant gas 
cylinder  

operating valve

(for R410A)

Gauge manifold 

valve (for R410A)

Charge hose 
(for R410A)

Refrigerant gas cylinder for R410A w ith siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

Union

Union

Union

4.  PURGING PROCEDURES, LEA  TEST, AND TEST RUN

Stop valve 

for GAS

Stop valve cap

(Torque 19.6 to 
29.4 N•m, 200 
to 300 kgf•cm)

Gauge manifold 

valve (for R410A)

Compound pressure 
gauge (for R410A)

–0.101MPa  
(–760 mmHg)

Handle 
Low

Handle High

Vacuum pump
(for R410A)

Close

Open

Hexagonal 
w rench

Stop valve 

for LIQUID

Pressure gauge
(for R410A)

Precautions w hen us-

ing the control valve

When attaching the control valve 

to the service port, valve core may 

deform or loosen if excess pres-
sure is applied. This may cause 
gas leak.

Service port

Charge hose 
(for R410A)

Body

Close

Open

Control 

valve

A

When attaching the control valve to 

the service port, ma e sure that the 

valve core is in closed position, and 

then tighten part A. Do not tighten 

part A or turn the body  hen valve 

core is in open position.

Service port cap

(Torque 13.7 to 
17.7 N•m, 140 to 
180 kgf•cm)

Charge hose 
(for R410A)

4-3. REMOVING THE MAINTENANCE PANEL

The setting of Dip Sw itch on the outdoor controller board can be changed 

ithout removing the front panel.

ollo  the procedures belo  to remove the maintenance panel and set 

the Dip Sw itch.

1) Remove scre (s)  hich fix the maintenance panel.

2) Remove the maintenance panel, and perform necessary settings.

3) Install the maintenance panel.

N o t e :

Ma e sure to fix the maintenance panel securely. Incomplete installation 

could cause malfunction.

Maintenance panel

 WARNING

W

h e n   o p e n i n g   o r  c l o s i n g   t h e   v a l v e  

b e l o w   fre e zi n g   t e m p e ra t u re s ,  
re fri g e ra n t   m a y   s p u rt   o u t   fro m   t h e  
g a p   b e t w e e n   t h e   v a l v e   s t e m   a n d   t h e  
v a l v e   b o d y ,   re s u l t i n g   i n   i n j u ri e s .

Cap

Valve stem

Valve body

Valve stem

VG79J997H01_01En.indd   6

2021/06/25   10:38:22

Summary of Contents for MXZ-2C20NA3

Page 1: ...ur Lors de l installation de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local M a n u a l d e i n s t a l a c i ó n Para el INSTALADOR En este manual só lo se describe la instalació n de la unidad exterior Para instalar la unidad interior consulte el manual d...

Page 2: ... dust blockage or loose parts on the pow er supply plug or the outlet it could cause electric shoc or fire If loose parts are found on the po er supply plug replace it S e c u re l y a t t a c h t h e e l e c t ri c a l c o v e r t o t h e i n d o o r u n i t a n d t h e s e rv i c e p a n e l t o t h e o u t d o o r u n i t If the electrical cover of the indoor unit and or the service panel of th...

Page 3: ... on the sides of the unit No obstacle above the unit F R E E S P A C E R E Q U I R E D A R O U N D O U T D O O R U N I T Service space When installing the unit in an area that is enclosed w ith w alls such as a verandah be sure to have enough space as sho n belo In this case the air conditioning capacity and pow er consumption might deteriorate When installing tw o or more units do not install the...

Page 4: ...VC pipe VP16 for drain socket 1 1 N o t e Place indoor outdoor unit connecting w ire B and pow er supply cord A at least 3 ft 1 m aw ay from the TV antenna w ire The ty for B to in the above table is quantity to be used per indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 500 mm if the front and both sides are open More than 3 15 16 in 100 mm More than 7 7 8 in 200 mm i...

Page 5: ... e c t ri c a l c o d e P O W E R S U P P L Y C A B L E Use solid or stranded conductor Min AWG8 Use copper conductors only F o l l o w l o c a l e l e c t ri c a l c o d e G R O U N D W I R E Use solid or stranded conductor Min AWG8 Use copper conductors only F o l l o w l o c a l e l e c t ri c a l c o d e W A R N I N G U s e t h e i n d o o r o u t d o o r u n i t c o n n e c t i n g w i re t h...

Page 6: ...sive tightening damages the flare section 1 Apply a thin coat of refrigeration oil G to the flared ends of the pipes and the pipe connections of the outdoor unit Do not apply refrigeration oil on screw threads Excessive tightening torque ill result in damage on the scre 2 or connection first align the center then tighten the first 3 to 4 turns of flare nut by hand 3 Tighten the flare nut ith a tor...

Page 7: ...ise the compressor w ill be locked To maintain the high pressure of the gas cylinder w arm the gas cylinder w ith w arm w ater under 104 40 C during cold season But never use na ed fire or steam Union Stop valve Liquid pipe Indoor unit Stop valve ith service port Gas pipe Refrigerant gas cylinder operating valve for R410A Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinde...

Page 8: ...w iring piping correction function w hich corrects w iring and piping combination When there is possibility of incorrect w iring and piping combination and confirming the combination is difficult use this function to detect and correct the combination by follo ing the procedures belo Make sure that the follow ing is done Pow er is supplied to the unit Stop valves are open N o t e During detection ...

Page 9: ...r la prise et la fiche Veillez à enfoncer à fond la fiche d alimentation d a n s l a p ri s e s e c t e u r La présence de poussière de saleté ou d éléments desserrés sur la fiche d alimentation ou la prise secteur peut entraîner un choc électrique ou un incendie Remplacez les éventuels éléments desserrés F i x e z c o rre c t e m e n t l e c o u v e rc l e d u b o î t i e r é l e c t ri q u e d e...

Page 10: ...cles se trouvent derrière lui et d un côté ou de l autre Absence d obstacle au dessus de l appareil 19 11 16 500 ou plus 7 7 8 200 ou plus 13 25 32 350 ou plus 3 15 16 100 ou plus 6 E s p a c e d e n t re t i e n Laissez un espace pour les travaux d entretien comme indiqué sur l illus tration 3 15 16 100 ou plus 19 11 16 500 ou plus 3 15 16 100 ou plus Espace d entretien 13 25 32 350 ou plus 13 25...

Page 11: ...Après le test de contrôle des fuites appliquer soigneusement du maté riau isolant pour obstruer les trous Si la tuyauterie doit être fixée sur un mur contenant des métaux de l étain p ex ou un treillis métal lique utiliser un morceau de bois traité d une épaisseur de 25 32 po 20 mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vin...

Page 12: ... t ri q u e l o c a l A V E R T I S S E M E N T U t i l i s e r l e c â b l e d e c o n n e x i o n c o n fo rm e a u x n o rm e s t e c h n i q u e s pour raccorder les unités interne et externe et fixer le câble fer m e m e n t s u r l a b l o c d e s o rt i e d e fa ç o n q u e l e c ô t é ra c c o rd e m e n t d e c e d e rn i e r n e s o i t s o u m i s à a u c u n e c o n t ra i n t e e x t ...

Page 13: ...Appliquez une fine couche d huile réfrigérante G sur les embouts évasés des tuyaux ainsi que sur les raccords de tuyauterie de l appareil extérieur N appliquez pas d huile réfrigérante sur les filetages Un couple de serrage excessif endommagera la vis 2 Pour effectuer le raccordement alignez d abord le centre puis serrez à la main l écrou à évasement de 3 à 4 tours 3 Serrez l écrou évasé avec une ...

Page 14: ...ce du robinet d arrêt à côté du conduit de gaz de l appareil extérieur 3 Mettez la pompe à vide en marche Faites le vide pendant 15 minutes minimum 4 Contrôlez la dépression ainsi obtenue avec la vanne du collecteur à jauge puis fermez la vanne et arrêtez la pompe à vide 5 Patientez pendant une minute ou deux Assurez vous que l aiguille de la vanne du collecteur à jauge reste dans la même position...

Page 15: ... p ro t e c t i o n c o n t re u n e re m i s e e n m a rc h e t ro p ra p i d e Lorsque le compresseur s arrête le dispositif de protection contre la remise en marche à trop brève échéance s enclenche Le compresseur restera arrêté trois minutes avant de se remettre en marche afin de protéger le climatiseur F o n c t i o n d e c o rre c t i o n d e c â b l a g e t u y a u t e ri e L appareil est é...

Page 16: ...as sueltas sustit yalo Fije firmemente la cubierta de la instalaci n eléctrica a la unidad interior y e l p a n e l d e s e rv i c i o a l a u n i d a d e x t e ri o r Si no se fijan con firmeza la cubierta de instalaci n eléctrica de la unidad interior y el panel de servicio de la unidad exterior podr a acumularse polvo agua etc en la unidad y producirse un incendio o una descarga eléctrica A l i...

Page 17: ... al viento se recomienda instalar una placa de flectora en el lado de salida de aire de la unidad exterior Para instalar el aparato de aire acondicionado evite los lugares siguientes donde es má s probable que ocurran problemas Donde pueda haber una fuga de gas inflamable Donde haya demasiado aceite para maquinaria En ambientes salobres como las zonas costeras Donde haya gas sulf rico como en zona...

Page 18: ...g 100 mm Má s de 7 7 8 pulg 200 mm si hay obstá culos a ambos lados Después de la prueba de fugas aplique material aislante de modo que no queden huecos Cuando los tubos deban instalarse en una pared con contenido metá lico placas de lat n o rejillas met licas ponga un trozo de madera tratada qu micamente de 25 32 pulg 20 mm o m s de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8...

Page 19: ...e s i n t e ri o r y e x t e ri o r c o n e l c a b l e d e c o n e x i ó n n o rm a lizado destinado a este fin y sujete bien el cable al panel de terminales d e m o d o q u e n o q u e d e t e n s o e n l a z o n a d e c o n e x i o n e s d e l p a n e l U n a conexi n y fijaci n defectuosas podr an provocar un incendio C o n e c t e l o s c a b l e s a l n ú m e ro c o rre s p o n d i e n t e d...

Page 20: ...do ya que podrí a deteriorar la secció n abocardada 1 Aplique una capa fina de aceite refrigerante G a los extremos abocardados de las tuberí as y de las conexiones de la tuberí a de la unidad exterior No aplique aceite de refrigeraci n en las roscas de los tornillos Un par de torsi n excesivo podrí a dañ ar el tornillo 2 Para hacer la conexi n alinee primero el centro y apriete las primeras 3 o 4...

Page 21: ...contrario puede bloquear el compresor Para mantener alta la presi n del cilindro de gas caliente el cilindro de gas con agua caliente a menos de 104 40 C en las estaciones fr as Nunca utilice fuego o vapor Unió n Vá lvula de retenció n Tuberí a de lí quido Unió n Unió n Unió n Unidad interior Vá lvula de reten ció n con abertura de servicio Tuberí a de gas Vá lvula de acciona miento del cilindro d...

Page 22: ...tinuaci n una vez que las unidades interior y exterior se hayan reubicado vuelva a recargar el sistema con la cantidad adecuada de refrigerante 7 Desactive el disyuntor Retire el medidor de presi n y las tuber as de refrigerante C u a n d o e l c i rc u i t o d e re fri g e ra c i ó n t i e n e u n a fu g a n o re a l i c e e l b o m b e o d e v a c i a d o c o n e l c o m p re s o r A l b o m b e...

Page 23: ...A4_white_tombo indd 1 2018 08 09 14 11 29 ...

Page 24: ...VG79J997H01 HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VG79J997H01_cover4 indd 2 2021 02 09 13 25 36 ...

Reviews: