20
Glass
terminal
OPERATING PROCEDURE
PHOTOS
3. Removing the propeller and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the propeller nut and the propeller.
NOTE : Loose the propeller in the rotating direction for
removal.
When attaching the propeller, align the mark on the
propeller and the motor shaft cut section.
Set the propeller in position by using the cut on the shaft
and the mark on the propeller.
(3) Remove the lead clamps and outdoor fan motor lead wires.
(4) Remove the screws fixing the outdoor fan motor.
(5) Remove the outdoor fan motor.
Photo 5
Propeller
Propeller
nut
Outdoor
fan motor
Set screws of the
outdoor fan motor
Hook
Relay panel
Outdoor fan motor lead wires
Set screws of the
outdoor fan motor
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the screws fixing the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover.
(5) Pull out the lead wires from the glass terminal of the com-
pressor.
(6) Recover gas from the refrigerant circuit.
NOTE :
Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
2
(0MPa).
(7) Disconnect the welded part of the suction pipe and
discharge pipe.
(8) Remove the nuts fixing the compressor.
(9) Remove the compressor.
Photo 6
Compressor
Suction pipe
Discharge pipe
Compressor
nuts
Photo : MU-A10ND -
C1
Photo : MU-A10ND -
C1
OB403B--1.qxp 07.6.26 10:28 AM Page 20