MXZ-2A30VA MXZ-2A40VA MXZ-2A52VA
<Control status>
The control performs when the all the following status are satisfied;
• When one or more indoor units are operating in HEAT mode. (Excluding thermostat OFF)
• When discharge temperature becomes 107
:
or more.
• When it passed 60 minutes or more since the operation has started or the last refrigerant recovery has controlled.
<Control details>
LEV opening of indoor unit not operating is controlled to be 80 pulse.
<Control finish status>
The control finishes either as follows. However, the LEV opening is considered to be 59 pulse.
• When it passed 60 seconds since the control has started.
• When the discharge temperature is 90
:
or less.
12-6. REFRIGERANT RECOVERY CONTROL ON HEATING
This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge
temperature thermistor.
(1) Compressor ON/OFF
When temperature of the discharge temperature thermistor exceeds 116
:
, the control stops the compressor.
When temperature of the discharge temperature thermistor is 80
:
(2A/3A/4A71/4A80VA
-
)/ 100°C (4A80VA
-
/5A) or
less, the controls starts the compressor.
(2) Compressor operation frequency
When temperature of the discharge temperature thermistor is expected to be higher than 116
:
, the control decreases 12Hz
from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 111
:
and less than 116
:
, the con-
trol decreases 6Hz from the current frequency.
When temperature of the discharge temperature thermistor is expected to be higher than 104
:
and less than 111
:
, the con-
trol is set at the current frequency.
E2
E1
12-5. DISCHARGE TEMPERATURE PROTECTION CONTROL
Fan speed is switched according to the number of operating indoor unit and the compressor frequency.
12-7. OUTDOOR FAN CONTROL
COOL
Up
Down
Up
Down
Mode
HEAT
Compressor frequency (Hz)
Fan speed
<Relation between compressor frequency and fan speed>
56
42
56
42
Up
Down
Fan speed
High
Low
Compressor frequency
Min.
Max.
40
30
40
30
MXZ-2A40VA-
MXZ-2A52VA
MXZ-3A54VA
MXZ-4A71/80VA-
MXZ-2A30VA
MXZ-2A40VA-
E2
E1
E2
50
40
50
40
MXZ-4A80VA-
MXZ-5A100VA
E1
Note
• When the indoor coil thermistor is 57
:
or more on HEAT operation, fan speed is fixed to Low speed.
Or, the indoor coil thermistor is 45
:
or less on HEAT operation, fan speed is back to normal.
OBT06D--6qxp 07.3.2 10:16 AM Page 161