89
5. R.V. coil control <MUH-A07/A09/A12WV>
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
When operation starts, the 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Compressor
R.V. coil
Outdoor fan
(COOL/DRY)
(HEAT)
5 sec.
5 sec.
Operation time chart
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
MUH type
25
:
or more
23
:
or more,
less than 25
:
less than 23
:
MU&MUX type
25
:
or more
more than13
:
,
less than 25
:
11-5. “I FEEL CONTROL” (
) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on
with a beep tone.
(2) Select “I FEEL CONTROL”(
) mode with the OPERA-
TION SELECT button.
(3) The operation mode is determined by the initial room tem-
perature at start-up of the operation, as shown on the
right table.
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
●
Once the mode is fixed, the mode does not change by room temperature afterwards.
●
Under the ON-TIMER (
) operation, mode is determined according to the room temperature at set time the opera-
tion starts.
●
When the system is stopped on the remote controller and restarted within 2 hours in “I FEEL CONTROL” (
) mode,
the system operates in previous mode automatically regardless of the room temperature.
Restart
COOL mode of
“I FEEL CONTROL”
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
or COOL mode
When the system is restarted after 2 hours and more, the operation mode is determined by the room temperature at
start-up of the operation.
Restart
COOL or DRY or
HEAT mode of “I FEEL
CONTROL” that deter-
mined by room tem-
perature at start-up of
the operation.
Operation time chart
Operation time chart