13-2. Instruction of troubleshooting
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Indoor unit
doesn't receive
the signal from
remote controller.
Indoor unit
operates.
But indoor
unit doesn't
blow out
cool air.
Indoor unit
operates.
Outdoor unit
doesn't operate
normally.
OPERATION
INDICATOR
lamp on the
indoor unit is
flashing on
and off.
Outdoor unit
operates in
only Test Run
operation.
Outdoor unit
doesn't
operate
even in
Test Run
operation.
Indoor unit
operates,
when the
EMERGENCY
OPERATION
switch is
pressed.
Indoor unit
doesn't operate,
when the
EMERGENCY
OPERATION
switch is
pressed.
Check room
temperature
thermistor.
Refer to
"Test point
diagram and
voltage" on
page 124.
MUH-A07/A09/A12WV
MUX-A19/A20/
A25/A26WV
Refer to
D
"Check of
outdoor unit"
on page 113
or 114.
Refer to
B
"Check of
remote
controller
and receiver
P.C. board"
on page 112.
MUH-A07/A09/A12WV
Flash on and
off at 0.5-
second
intervals
Cause:
Indoor/
Outdoor unit
• Mis-wiring
2-time flash
Cause:
Indoor unit
• Trouble of
room temp-
erature/
indoor coil
thermistor
3-time flash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
6-time flash
Cause:
Outdoor unit
• Trouble of
thermistor
in outdoor
unit
7-time flash
Cause:
Outdoor unit
• Trouble of
outdoor
control
system
Check room
temperature
thermistor
and indoor
coil thermis-
tor.
Refer to
"Test point
diagram and
voltage"
on page 124.
Refer to
A
"Check of
indoor fan
motor"
on page 112.
MUH-A07/A09/A12WV
Refer to
H
"Check of
outdoor
thermistor"
on page 118.
MUH-A07/A09/A12WV
Replace the
deicer
P.C. board.
MUH-A07/A09/A12WV
1-time flash
Cause:
Outdoor /
Indoor unit
• Trouble of
serial signal
Refer to
G
"How to check
mis-wiring and serial signal
error (When outdoor unit
doesn't work)" on page 117.
W
1
1. Check indoor /
outdoor
connecting wire.
2. Refer to
C
"Check of indoor
electronic control
P.C. board"
on page 113.
Outdoor unit
doesn't
stop even
if indoor unit
stops.
Unit doesn't
operate
normal
operation in
COOL or
HEAT mode.
MU/H-A07/A09/A12WV
Refer to
E
"Check of
outdoor unit"
on page 115.
MUH-A07/A09/A12WV
Refer to
F
"Check of
R.V. coil"
on page 116.
MUX-A10/A19/A20/
A25/A26WV
Refer to
I
"Check of
indoor/outdoor
units' connection
and outdoor unit"
on page 118.
W
1.<The case of the trouble of the serial signal>
When the power is turned off and then turned on again, the indication shows “the trouble of mis-wiring”.
MSC-A07WV -
MU-A07WV -
MUH-A07WV -
MUX-A10WV -
MUX-A25WV -
MSC-A09WV -
MU-A09WV -
MUH-A09WV -
MUX-A19WV -
MUX-A26WV -
MSC-A12WV -
MU-A12WV -
MUH-A12WV -
MUX-A20WV -
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1
E1