Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M
"
.
1
Turn on the main power to the unit.
2
Press the button twice continuously.
(Start this operation from the turned off status of remote controller
display.)
and current operation mode are displayed.
3
Press the ( ) button to activate mode, then
check whether cool air is blown out from the unit.
4
Press the ( ) button to activate mode, then
check whether warm air is blown out from the unit.
5
Press the button and check whether strong air is blown out
from the unit.
6
Press the button and check whether the auto vane operates
properly.
7
Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps
2
to
7
.
• It is not possible to run in FAN, DRY or AUTO mode.
MODE
MODE
COOL
HEAT
TEST RUN
FAN
VANE
TEST RUN