83
SW2 setting
Display detail
Explanation for display
Unit
degF
0~327 (0~182degC)
(When the temperature is 100degF or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 150degF;
0.5 secs. 0.5 secs. 2 secs.
Sub cool on error occurring. SC
0~234
Cooling = TH6-TH3
Heating = TH5-TH2
0~234 (0~130degC)
(When the temperature is 100degF or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 115degF;
0.5 secs. 0.5 secs. 2 secs.
Thermostat-on time until error stops
0~999
0~999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 secs. 0.5 secs. 2 secs.
50
1
1
ON
2 3 4 5 6
Discharge superheat on error occurring
SHd
0~327
Cooling = TH4 (or TH32)-TH6
Heating = TH4 (or TH32)-TH5
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
degF
Minute
15
1
15
4
1
ON
2 3 4 5 6
Normal
Overvoltage error
Undervoltage error
Input current sensor error.
L1 or L2-phase open error.
Abnormal power synchronous signal
PFC error (A12, 18, 24NHA)
(Overvoltage/Undervoltage/Overcurrent)
PFC/ACTM error
Undervoltage
Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
L
1
phase open error (04) + PFC error (10) = 14
Power circuit board
Controller circuit board
Controller circuit board
Power circuit board
Power circuit board
Check CNAF wiring.
Defective ACTM/P.B.
–
Description
Detection point
Display
00
01
02
04
08
10
20
U9 Error status during the Error
postponement period
Code
display
The black square (
■
) indicates a switch position.