10-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on>
(Note 1) Refer to indoor unit section for code P and code E.
Error Code
Abnormal point and detection method
Case
Judgment and action
None
—
1
No voltage is supplied to terminal
block (TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or disconnec-
tion of power supply terminal
c) Open phase (L1 or L2 phase)
2
Electric power is not charged to
power supply terminal of out-
door power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
A12-A24N :Disconnection of
connector R or S
A30-A42N :Disconnection of
connector TABT or TABS
3
Electric power is not supplied to
outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
4
Disconnection of reactor (DCL
or ACL)
5
Disconnection of outdoor noise
filter circuit board or parts fail-
ure in outdoor noise filter circuit
board
As for A30-A42N type, it is
especially needed to check the
resistance RS1 on the noise
filter circuit board.
6
Defective outdoor power circuit
board
7
Defective outdoor controller
circuit board
1
Check following items.
a) Power supply breaker
b) Connection of power supply terminal block
(TB1)
c) Connection of power supply terminal block
(TB1)
2
Check following items.
a) Connection of power supply terminal block
(TB1)
b) Connection of terminal on outdoor power
circuit board
A12-A24N: Disconnection of connector R or S
Refer to 10-9.
A30-A42N: Disconnection of connector TABT
or TABS
Refer to 10-9.
3
Check
connection of the connector (CNDC)
on the outdoor controller circuit board.
Check
connection of the connector, LD1 and
LD2 for A12-A24N and CNDC for A30-A36N,
on the outdoor power circuit board.
Refer to 10-9.
4
Check
connection of reactor. (DCL or ACL)
A12-A24N: Check connection of “LO” and
“NO” on the outdoor noise filter circuit board.
Check connection of “R” and “S” on the
outdoor power circuit board.
A30-A42N: Check connection of “L1” and “L2”
on the active filter module. (ACTM)
Refer to 10-9.
5
a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 10-9.
6
Replace outdoor power circuit board.
7
Replace controller board (When items above
are checked but the units cannot be repaired).
F3
(5202)
63L connector open
Abnormal if 63L connector circuit is open for
3 minutes continuously after power supply.
63L: Low-pressure switch
<A42N only>
1
Disconnection or contact failure
of 63L connector on outdoor
controller circuit board
2
Disconnection or contact failure
of 63L
3
63L is operating due to refriger-
ant leakage or defective parts.
4
Defective outdoor controller
circuit board
1
Check connection of 63L connector on
outdoor controller circuit board.
Refer to 10-9.
2
Check the 63L side of connecting wire.
3
Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
4
Replace outdoor controller circuit board.