67
1
ON
2 3 4 5 6
°C
Discharge superheat SHd
0 – 255
TH4 - 63HS
0 – 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
0.1 A
Input current of outdoor unit
0 – 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
Step
Sub cool step
1 – 5
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
°C
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor setting temperature
17 – 30
Outdoor pressure sensor saturated
temperature (63HS)
-39 – 88
Outdoor heatsink temperature (TH8)
-40 – 200
17 – 30
°C
°C
°C
-39 – 88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
-40 – 200
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
(When the thermistor detects 100
:
or more,
hundreds digit, tens digit and ones digit are displayed
by turns.)
Outdoor temperature (TH7)
-39 – 88
-39 – 88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
(No error)
Overvoltage error
Undervoltage error
Input current sensor error
L
1
-phase open error
Abnormal power synchronous signal
PFC error
(Overvoltage / Undervoltage / Overcurrent)
PFC/ IGBT error
(Undervoltage)
* Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
L
1
phase open error (04) + PFC error (10) = 14
Description
Display
00
01
02
04
08
10
20
Code
display
1
ON
2 3 4 5 6
2 cycles
0 – FFFE (in hexadecimal notation)
(When more than FF in hex (255 in decimal), the
number is displayed in order of 16
3
's and 16
2
's, and
16
1
's and 16
0
's places.
(Example) When 5000 cycles;
0.5 secs. 0.5 secs. 2 secs.
C4
9
The black square ( ) indicates a switch position.
U9 error detail history (latest)
Number of defrost cycles
0 – FFFE
OCH544