103
Photo 12
Photo 14
14. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the cover panel (front) fixing screws (2 for front, 5
× 12) and remove the cover panel (front). (See Photo 13)
(4) Remove the cover panel (rear) fixing screws (2 for rear, 5
× 12) and remove the cover panel (rear). (See Photo 13)
(5) Remove the electrical parts box. (See Photo 4)
(6) Remove the valve bed fixing screws (3 for front, 4 × 10) and
the ball valve and stop valve fixing screws (4 for front, 5 ×
16) and then remove the valve bed.
(7) Remove the side panel (R). (See Photo 1)
(8) Remove the separator fixing screws (3 for front, 4 × 10)
and remove the separator.
(9) Recover refrigerant.
(10) Remove the 3 points of the compressor fixing nut using a
spanner or a adjustable wrench.
(11) Remove the welded pipe of compressor inlet and outlet
then remove the compressor.
Note: Recover refrigerant without spreading it in the air.
15. Removing the accumulator
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the cover panel (front). (See Photo 13)
(4) Remove the cover panel (rear). (See Photo 13)
(5) Remove the electrical parts box. (See Photo 4)
(6) Remove the valve bed. (See Photo 12)
(7) Remove the side panel (R). (See Photo 1)
(8) Recover refrigerant.
(9) Remove 4 welded pipes of accumulator inlet and outlet.
(10) Remove the receiver leg fixing screws (2 for front, 4 × 10).
Note: Recover refrigerant without spreading it in the air.
Cover panel
(Front)
Cover panel
(Rear)
Photo 13
Cover panel
(Front) fixing
screws
Power
receiver
Compressor
Valve bed
Separator
fixing screw
Separator
Compressor
fixing nut
Valve bed
fixing screws
Valve bed
fixing screw
Accumulator leg
fixing screws
Accumulator
Accumulator
leg
Inlet
Outlet
OPERATING PROCEDURE
PHOTOS
OCH544