5-4. STANDARD OPERATION DATA
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/cm²)
Representative matching
PEAD-RP71JA
Plate HEX
ACH70-40
Mode
ATA Cooling
ATA Heating
ATW Heating
HR Cooling
Total
ATA capacity
W
7,100
8,000
—
7,100
ATW capacity
W
—
—
8,000
9,000
Input
kW
2.10
2.09
1.96
3.22
COP
3.38
3.83
4.08
5.00
Electrical circuit
Indoor unit
PEAD-RP71JA
Phase, Hz
1 , 50
1 , 50
—
1 , 50
Voltage
V
230
230
—
230
Current
A
0.17
0.15
—
0.17
Outdoor unit
PUHZ-FRP71VHA
Phase, Hz
1 , 50
1 , 50
1 , 50
1 , 50
Voltage
V
230
230
230
230
Current
A
9.15
9.12
8.70
13.97
Refrigerant circuit
Discharge pressure
MPa
2.79
2.46
2.13
3.39
Suction pressure
MPa
0.96
0.71
0.70
0.94
Discharge temperature
°C
71
62
53
80
Condensing temperature
°C
47
42
37
57
Suction temperature
°C
10
0
0
9
Ref. pipe length
m
5 + 5
5 + 5
5 + 5
5 + 5
AT
A indoor side
Intake air temperature
DB
°C
27
20
—
27
WB
°C
19
15
—
19
Discharge air temperature
DB
°C
14.5
36
—
14.5
ATW side
Return temperature
°C
—
—
30
50
Flow temperature
°C
—
—
35
55
Flow rate
L/min
—
—
23
23
Outdoor side
Intake air temperature
DB
°C
35
7
7
35
WB
°C
24
6
6
24
SHF
0.81
—
—
0.81
BF
0.11
—
—
0.11
OCH544