background image

7

4. Installing the refrigerant piping

A

 Service port

B

 Open/Close section

Local pipe

Fig. 4-4

4.4. Refrigerant pipe airtight testing method (Fig. 4-4)

(1) Connect the testing tools.
 •  

Make sure the stop valves are closed and do not open them.

 •  

Add pressure to the refrigerant lines through the service port 

A

 of the liquid 

stop valve.

(2)  Do not add pressure to the specifi ed pressure all at once; add pressure little by 

little.

 

1

  Pressurize to 0.5 MPa (5 kgf/cm

2

G), wait five minutes, and make sure the 

pressure does not decrease.

 

2

  Pressurize to 1.5 MPa (15 kgf/cm

2

G), wait fi ve minutes, and make sure the 

pressure does not decrease.

 

3

  Pressurize to 4.15 MPa (41.5 kgf/cm

2

G) and measure the surrounding tem-

perature and refrigerant pressure.

(3)  If the specifi ed pressure holds for about one day and does not decrease, the 

pipes have passed the test and there are no leaks.

 •  

If the surrounding temperature changes by 1 °C, the pressure will change by 
about 0.01 MPa (0.1 kgf/cm

2

G). Make the necessary corrections.

(4)  If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the 

source of the gas leak.

4.5. Stop valve opening method (Fig. 4-5)

The stop valve opening method varies according to the outdoor unit model. Use the 
appropriate method to open the stop valves.

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.

 

 (ø9.52: Approximately 10 revolutions)

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

Refrigerant pipes are protectively wrapped
•  

The pipes can be protectively wrapped up to a diameter of ø90 before or after 
connecting the pipes. Cut out the knockout in the pipe cover following the groove 
and wrap the pipes. 

Pipe inlet gap
•  

Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-
main. (If the gaps are not closed, noise may be emitted or water and dust will 
enter the unit and breakdown may result.)

4.6. Addition of refrigerant

•  

Additional charging is not necessary if the total pipe length does not exceed 30 m.

•  

If the total pipe length exceeds 30m, charge the unit with additional R410A re-
frigerant according to the permitted pipe lengths in the chart shown on the right.

 *  

When the unit is stopped, charge the unit with the additional refrigerant 
through the liquid stop valve after the pipe extensions and indoor unit have 
been vacuumized.

 

 

 When the unit is operating, add refrigerant to the gas check valve using a 
safety charger. Do not add liquid refrigerant directly to the check valve.

 *  

After charging the unit with refrigerant, note the added refrigerant amount on 
the service label (attached to the unit).

 

 

 Refer to the “1.5. Using R410A refrigerant air conditioners” for more informa-
tion.

•  Be careful when installing multiple units. Connecting to an incorrect indoor unit 

can lead to abnormally high pressure and have a serious effect on operation 
performance.

Permitted pipe 

length (total)

Permitted vertical 

difference

Additional refrigerant charging amount 

(total)

31 - 40 m

41 - 50 m

51-60

-60 m

-20 m

0.6 kg

1.2 kg

1.8 kg

* The total pipe length equals the indoor-outdoor pipe length plus the 

cylinder- or hydrobox-outdoor pipe length. The max. pipe length for 
each side is 30 m.

Precautions when using the charge valve (Fig. 4-6)

Do not tighten the service port too much when installing it, otherwise, the valve 
core could be deformed and become loose, causing a gas leak.
After positioning section 

B

 in the desired direction, turn section 

A

 only and tighten 

it.
Do not further tighten sections 

A

 and 

B

 together after tightening section 

A

.

*  The fi gure to the left is an example 

only.

   The stop valve shape, service port 

position, etc., may vary according to 
the model.

* Turn section 

A

 only.

   (Do not further tighten sections 

A

 

and 

B

 together.)

C

 Charge hose

D

 Service port

A

B

C

D

Fig. 4-6

E

D

C

B

A

Stop valve

Fig. 4-5

H

 Double spanner section

 

 (Do not apply a spanner other than to this 
section. Doing so would cause coolant leaks.)

Seal section

 

 (Seal the end of the heat insulation material at 
the pipe connection section with whatever seal 
material you have on hand so that water does 
not infi ltrate the heat insulation material.)

A

 Valve

B

 Unit side

Cap

D

 Local pipe side

E

 Pipe cover

F

 Service port

G

 Wrench hole

Sealed, same way for gas

 

side

Pipe cover

Summary of Contents for Mr.Slim PUHZ-FRP71VHA

Page 1: ...anuale ed il manuale d installazione dell unità interna prima di installare l unità esterna Il testo originale è redatto in lingua Inglese Le altre versioni linguistiche rappresentano traduzioni dell originale MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade interior antes de instalar o aparelho de unidade exterior O idioma...

Page 2: ... high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized ...

Page 3: ...nt pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 2 Installation location Fig 2 1 2 1 Refrigerant pipe Fig 2 1 Check that the difference between the heights of the i...

Page 4: ...ide In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 4 Obstacles at front and rear only Fig 2 15 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance should be 500 mm or more 6 Multiple parallel unit arrangement Fig 2 17 When using an optiona...

Page 5: ...round Max 30 B A C E D 600 Min 360 600 Min 10 175 950 175 25 330 370 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipe...

Page 6: ...2 screws 1 Perform refrigerant piping connections for the indoor outdoor unit and the cyl inder outdoor unit or hydrobox outdoor unit when the outdoor unit s stop valves are completely closed 2 Vacuum purge air from the indoor unit and the cylinder unit or hydrobox and the connection piping 3 After connecting the refrigerant pipes check the connected pipes the indoor unit and the cylinder unit or ...

Page 7: ...ry if the total pipe length does not exceed 30 m If the total pipe length exceeds 30m charge the unit with additional R410A re frigerant according to the permitted pipe lengths in the chart shown on the right When the unit is stopped charge the unit with the additional refrigerant through the liquid stop valve after the pipe extensions and indoor unit have been vacuumized When the unit is operatin...

Page 8: ...s are used for gas or oil heat pump systems use new pipes The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping Drain socket PAC SG61DS E Drain pan PAC SG64DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option 4 8 For twin indoor units combination ...

Page 9: ...al code 2 Power supply cords the Indoor Outdoor connecting cable and the Cylinder or Hydrobox Outdoor connecting cable shall not be lighter than polychlo roprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied 6 Electrical work A Control Outdoor Unit S1 S2 S3 S1 S2 S3 3 poles isolato...

Page 10: ...4 in outdoor unit SW4 1 ON Cooling operation SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The linear expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of th...

Page 11: ...ically in 5 minutes 6 Turn off the main power Warning Do not disconnect extension pipes during the refrigerant collecting operation is running If you open the stop valves to the air during the compressor is running the pressure could be abnormal high level and this may cause a rupture of the compressor or other hazardous situation Use a refrigerant recovery machinery if the refrigerant collecting ...

Page 12: ...n omalla vastuullaan että seuraavassa kuvattavat asuinkiinteistöihin liikekiinteistöihin ja kevyen teollisuuden ympäristöihin tarkoitetut ilmastointilaitteet ja lämpö pumput MITSUBISHI ELECTRIC PUHZ FRP71VHA 1 2 3 9 Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remarque Le numéro de série de l appareil se trouve sur...

Page 13: ...atterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging veroorzaken Installeer het apparaat op een stabiele structuur om overmatig lawaai of trillingen te voorkomen Het niveau van de geluidsdruk ligt onder 70 dB A Dit apparaat is bedoeld voor gebruik door ervaren of opgeleide gebruikers in werkplaatsen in de lichte industrie en op boerderijen of...

Page 14: ...00 100 500 150 100 1000 300 Max 500 200 1000 300 1000 Max 300 1000 1000 300 500 400 1000 100 1000 400 2000 300 1000 500 150 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 ...

Page 15: ...ET UXBRIDGE MIDDLESEX UB8 1QQ U K This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC RoHs Directive 2011 65 EU ...

Reviews: