background image

S3

S3

S2

S1

S2

S1

L N

For Power

S3

S3

S2

S1

S2

S1

For Power

I

J

J

G

F

9

6.2. Field electrical wiring

Outdoor unit power supply

~/N (single), 50 Hz, 230 V

Outdoor unit input capacity Main switch (Breaker)

*1

25 A

Wiring 

Wire No. × 

size (mm

2

)

Outdoor unit power supply

3 × Min. 2.5

Indoor unit-Outdoor unit
Cylinder- or Hydrobox-Outdoor unit

*2

3 × 1.5 (Polar)

Indoor unit-Outdoor unit earth
Cylinder- or Hydrobox-Outdoor unit earth.

*2

1 × Min. 1.5

Remote controller-Indoor unit
Cylinder- or Hydrobox-side remote controller-its unit

*3

2 × 0.3 (Non-polar)

Circuit rating

Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)

*4

AC 230 V

Indoor unit-Outdoor unit S1-S2
Cylinder- or Hydrobox-Outdoor unit S1-S2

*4

AC 230 V

Indoor unit-Outdoor unit S2-S3
Cylinder- or Hydrobox-Outdoor unit S2-S3

*4

DC 24 V

Remote controller-Indoor unit
Cylinder- or Hydrobox-side remote controller--its unit

*4

DC 12 V

*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
 

Make sure that the current leakage breaker is one compatible with higher harmonics.

 

Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.

 

The use of an inadequate breaker can cause the incorrect operation of inverter.

*2. Max. 45 m
 

If 2.5 mm

2

 used, Max. 50 m

 

If 2.5 mm

2

 used and S3 separated, Max. 80 m

*3. The 10 m wire is attached in the remote controller accessory.
*4.  The fi gures are NOT always against the ground.
 

S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national code.
   2. 

 

Power supply cords, the Indoor-Outdoor connecting cable and the Cylinder- or Hydrobox-Outdoor connecting cable shall not be lighter than polychlo-
roprene sheathed fl exible cord. (Design 60245 IEC 57)

 

 

 

3.  Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.

6. Electrical work

A-Control

Outdoor Unit

S1

S2

S3

S1

S2

S3

3 poles isolator

Power supply

Isolator

A-Control

Indoor Unit

Cylinder unit 

or Hydrobox

 Warning:

·   In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between 

power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when 
the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.

6.1. Outdoor unit (Fig. 6-1, Fig. 6-2)

 

1

 Remove the service panel.

 

2

 Wire the cables referring to the Fig. 6-1 and the Fig. 6-2.

Fig. 6-1

A

 Indoor unit

B

 Outdoor unit

C

 Remote controller

D

 Main switch (Breaker)

E

 Earth

Terminal block for power (L, N,  ) and Indoor-Outdoor connection (S1, S2, S3)

Terminal block for Cylinder unit- or Hydrobox-Outdoor connection (S1, S2, S3)

Service panel

Clamp

*    Clamp the cables so that they do not contact the center of the service panel or 

the gas valve.

Earth terminal for Indoor unit and either Cylinder unit or Hydrobox

K

  Cylinder unit or Hydrobox

L

  Remote controller for Cylinder unit or Hydrobox

Note : 
If the protective sheet for the electrical box is removed during servicing, be sure to 
reinstall it.

 Caution:

Be sure to install N-Line. Without N-Line, it could cause damage to unit.

F

G

H

Never splice the power cable or the indoor-outdoor, cylinder/hydro-outdoor connection cable, otherwise it may result in a smoke, a fi re or communication failure.

Fig. 6-2

Summary of Contents for Mr.Slim PUHZ-FRP71VHA

Page 1: ...anuale ed il manuale d installazione dell unità interna prima di installare l unità esterna Il testo originale è redatto in lingua Inglese Le altre versioni linguistiche rappresentano traduzioni dell originale MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade interior antes de instalar o aparelho de unidade exterior O idioma...

Page 2: ... high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized ...

Page 3: ...nt pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 2 Installation location Fig 2 1 2 1 Refrigerant pipe Fig 2 1 Check that the difference between the heights of the i...

Page 4: ...ide In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 4 Obstacles at front and rear only Fig 2 15 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance should be 500 mm or more 6 Multiple parallel unit arrangement Fig 2 17 When using an optiona...

Page 5: ...round Max 30 B A C E D 600 Min 360 600 Min 10 175 950 175 25 330 370 4 1 Precautions for devices that use R410A refrigerant Refer to 1 5 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipe...

Page 6: ...2 screws 1 Perform refrigerant piping connections for the indoor outdoor unit and the cyl inder outdoor unit or hydrobox outdoor unit when the outdoor unit s stop valves are completely closed 2 Vacuum purge air from the indoor unit and the cylinder unit or hydrobox and the connection piping 3 After connecting the refrigerant pipes check the connected pipes the indoor unit and the cylinder unit or ...

Page 7: ...ry if the total pipe length does not exceed 30 m If the total pipe length exceeds 30m charge the unit with additional R410A re frigerant according to the permitted pipe lengths in the chart shown on the right When the unit is stopped charge the unit with the additional refrigerant through the liquid stop valve after the pipe extensions and indoor unit have been vacuumized When the unit is operatin...

Page 8: ...s are used for gas or oil heat pump systems use new pipes The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping Drain socket PAC SG61DS E Drain pan PAC SG64DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option 4 8 For twin indoor units combination ...

Page 9: ...al code 2 Power supply cords the Indoor Outdoor connecting cable and the Cylinder or Hydrobox Outdoor connecting cable shall not be lighter than polychlo roprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied 6 Electrical work A Control Outdoor Unit S1 S2 S3 S1 S2 S3 3 poles isolato...

Page 10: ...4 in outdoor unit SW4 1 ON Cooling operation SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The linear expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of th...

Page 11: ...ically in 5 minutes 6 Turn off the main power Warning Do not disconnect extension pipes during the refrigerant collecting operation is running If you open the stop valves to the air during the compressor is running the pressure could be abnormal high level and this may cause a rupture of the compressor or other hazardous situation Use a refrigerant recovery machinery if the refrigerant collecting ...

Page 12: ...n omalla vastuullaan että seuraavassa kuvattavat asuinkiinteistöihin liikekiinteistöihin ja kevyen teollisuuden ympäristöihin tarkoitetut ilmastointilaitteet ja lämpö pumput MITSUBISHI ELECTRIC PUHZ FRP71VHA 1 2 3 9 Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remarque Le numéro de série de l appareil se trouve sur...

Page 13: ...atterijen in uw mond om inslikking te voorkomen Het inslikken van batterijen kan verstikking of vergiftiging veroorzaken Installeer het apparaat op een stabiele structuur om overmatig lawaai of trillingen te voorkomen Het niveau van de geluidsdruk ligt onder 70 dB A Dit apparaat is bedoeld voor gebruik door ervaren of opgeleide gebruikers in werkplaatsen in de lichte industrie en op boerderijen of...

Page 14: ...00 100 500 150 100 1000 300 Max 500 200 1000 300 1000 Max 300 1000 1000 300 500 400 1000 100 1000 400 2000 300 1000 500 150 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 ...

Page 15: ...ET UXBRIDGE MIDDLESEX UB8 1QQ U K This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC RoHs Directive 2011 65 EU ...

Reviews: