40
1
In COOL and DRY operation
2
In FAN operation
Vane angle is fixed to Angle 1.
Vane angle is fixed to Angle 4.
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When the OPERATE/STOP(ON/OFF) button is pressed. (POWER ON/OFF)
(b) When the vane control is changed AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
(4) VANE AUTO mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
(5) STOP (operation OFF) and ON-TIMER standby
When the following cases occur, the vane returns to the closed position.
(a) When the OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When the ON-TIMER is on standby.
(6) Dew prevention
During COOL or DRY operation at vane Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour,
the vane angle automatically changes to Angle 1 for dew prevention.
(7) SWING MODE
<MS09NW, MS12/15/17NN>
By pressing the SWING (
) button the horizontal vane swings vertically. The remote controller displays “
”. SWING
mode is cancelled when the SWING (
) button or the VANE CONTROL (
) button is pressed or the mode is
changed to other mode.
<MS09NW2, MS12/15/17NN2>
By selecting SWING mode with the VANE CONTROL (
) button, the horizontal vane swings vertically. The remote
controller displays “
”. SWING mode is cancelled when the VANE CONTROL (
) button is pressed once again.
SWING
SWING
VANE
VANE
VANE