58
MUM30NN2
SYSTEM
52C CONTACTOR
OUTDOOR FAN RELAY
Triple
All three : ON
X61 is ON
Double
Two of them : ON
X62 is ON
Single
One of them : ON
X63 is ON
OPERATION OF 52C1, 52C2, 52C3, X61, X62, X63
NOTE
1 : Compressor is on while 52C is on.
2 : Compressor is off while 52C is off.
3: Relay of X61~X63 can not turn on at the same time.
52C1
52C2
52C3
X61
X62
X63
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
OFF
FAN RELAY / FAN SPEED / APPLIED VOLTAGE
FAN MOTOR RELAY
OUTDOOR FAN SPEED
(MF1/MF2)
APPLIED VOLTAGE TO FAN
X61 is ON
Hi/Hi
230V AC between WHT and BLK
X62 is ON
Lo/Lo
230V AC between WHT and BLU
X63 is ON
Lo/Lo
230V AC between WHT and BLU