25
3. Outdoor unit failure mode table
MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA
The left lamp of OPERA-
TION INDICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C.
board)
Condition Remedy
Indoor/outdoor
unit failure mode
recall function
LED 1
LED 2
OFF Non
(Normal)
Lighting
Lighting
—
—
—
2-time
fl
ash
Outdoor power system
Lighting Lighting
IPM protection stop or lock protection stop is continuously
performed 3 times within 1 minute after the compres-
sor gets started, or converter protection stop or bus-bar
voltage protection stop is continuously performed 3 times
within 3 minutes after start-up.
Check the connection of the
compressor connecting wire.
Refer to 10-5. "How to check
inverter/compressor".
Refer to 10-5. "Check of
compressor start failure".
Check the stop valve.
•
•
•
•
○
3-time
fl
ash
Discharge temperature thermistor Lighting
Once
Thermistor shorts or opens during compressor running.
Refer to 10-5. "Check of
outdoor thermistors".
•
○
Defrost thermistor (MUZ)
Lighting
Once
Ambient temperature thermistor
Lighting
Twice
Fin temperature thermistor
Lighting 3 times
P.C. board temperature thermistor Lighting 4 times
Replace the outdoor electronic
control P.C. board.
•
Outdoor heat exchanger tempera-
ture thermistor
Lighting 9
times
Refer to 10-5. "Check of
outdoor thermistors".
•
4-time
fl
ash
Overcurrent
Once
Goes
out
28 A current
fl
ow into intelligent power module.
Reconnect compressor con-
nector.
Refer to 10-5. "How to check
inverter/compressor."
Refer to 10-5. "Check of
compressor start failure".
Check the stop valve.
•
•
•
•
—
5-time
fl
ash
Discharge temperature
Lighting Lighting
Temperature of discharge temperature thermistor exceeds
241°F (116°C), compressor stops. Compressor can restart
if discharge temperature thermistor reads 212°F (100°C)
or less 3 minutes later.
Check refrigerant circuit and
refrigerant amount.
Refer to 10-5. "Check of
LEV".
•
•
—
6-time
fl
ash
High pressure
Lighting Lighting
The outdoor heat exchanger temperature exceeds 158°F
(70°C) during cooling or the indoor gas pipe temperature
exceeds 158°F (70°C) during heating (MUZ).
Check refrigerant circuit and
refrigerant amount.
Check the stop valve.
•
•
—
7-time
fl
ash
Fin temperature
3 times
Goes
out
The
fi
n temperature exceeds 189°F (87°C) during opera-
tion.
Check around outdoor unit.
Check outdoor unit air pas-
sage.
Refer to 10-5. "Check of
outdoor fan motor".
•
•
•
—
P.C. board temperature
4 times
Goes
out
The P.C. board temperature exceeds 158°F (70°C) during
operation.
8-time
fl
ash
Outdoor fan motor
Lighting Lighting Failure occurs continuously 3 times within 30 seconds
after the fan gets started.
Refer to 10-5. "Check of
outdoor fan motor".
•
—
9-time
fl
ash
Nonvolatile memory data
Lighting 5 times Nonvolatile memory data cannot be read properly.
Replace the outdoor electronic
control P.C. board.
•
○
10-time
fl
ash
Discharge temperature
Lighting Lighting
The frequency of the compressor is kept 80 Hz or more
and the discharge temperature is kept under 102°F (39°C)
for more than 20 minutes.
Check refrigerant circuit and
refrigerant amount.
Refer to 10-5. "Check of
LEV".
•
•
—
11-time
fl
ash
Communication error between
P.C. boards
Lighting 6
times
Communication error occurs between the electronic control
P.C. board and power board for more than 10 seconds.
Check the connecting wire
between outdoor electronic
control P.C. board and power
board.
•
—
The communication between boards protection stop is
continuously performed twice.
○
Current sensor
Lighting 7 times
A short or open circuit is detected in the current sensor
during compressor operating.
Replace the power board.
•
—
Current sensor protection stop is continuously performed
twice.
○
Zero cross detecting circuit
5 times Goes out
Zero cross signal cannot be detected while the compres-
sor is operating.
Check the connecting wire
among electronic control P.C.
board, noise
fi
lter P.C. board
and power board.
•
—
The protection stop of the zero cross detecting circuit is
continuously performed 10 times.
○
NOTE
: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).
Summary of Contents for Mr.Slim MSY-D30NA
Page 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Page 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Page 43: ...9 MUY D30NA MUY D36NA ...
Page 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Page 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Page 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Page 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Page 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Page 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Page 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Page 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Page 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Page 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Page 148: ...22 MUY GE18NA 1 OBH549G ...
Page 149: ...23 MUZ GE24NA OBH549G ...
Page 150: ...24 MUY GE24NA OBH549G ...
Page 199: ...73 OBH549G ...