![Mitsubishi Electric Mr.Slim MSY-D30NA Service Manual Download Page 153](http://html.mh-extra.com/html/mitsubishi-electric/mr-slim-msy-d30na/mr-slim-msy-d30na_service-manual_240592153.webp)
27
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft.
Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas
Liquid
MUZ-GE09/12/15NA/NA2
MUZ-GE09/12/15NAH/NAH2
MUY-GE09/12/15NA/NA2
65 40
3/8
(GE09/12)
1/2
(GE15)
1/4
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
100 50
1/2
MUZ-GE24NA
MUY-GE24NA
100
50
5/8
3/8
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE
: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
65
MUZ-GE09NA/NA2
MUZ-GE09NAH/NAH2
MUY-GE09NA/NA2
1 lb. 12 oz.
0
1.62
4.86
8.10
11.34
12.96
MUZ-GE12NA/NA2
MUZ-GE12NAH/NAH2
MUY-GE12NA/NA2
2 lb. 9 oz.
MUZ-GE15NA/NA2
MUZ-GE15NAH/NAH2
MUY-GE15NA/NA2
Calculation: X oz. = 1.62/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25
30
40
50
60
70
80
90
100
MUZ-GE18NA
MUZ-GE18NAH
MUY-GE18NA
3 lb. 7 oz.
0
1.08
3.24
5.40
7.56
9.72
11.88
14.04
16.20
Calculation: X oz. = 1.08/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
NOTE
: Refrigerant piping exceeding 33 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
33
40
50
60
70
80
90
100
MUZ-GE24NA
MUY-GE24NA
4 lb. 3 oz.
0
4.14
10.06
15.98
21.90
27.82
33.74
39.66
Calculation: X oz. = 2.96/5 oz. / ft. × (Refrigerant piping length (ft.) - 33)
OBH549G
Summary of Contents for Mr.Slim MSY-D30NA
Page 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Page 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Page 43: ...9 MUY D30NA MUY D36NA ...
Page 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Page 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Page 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Page 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Page 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Page 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Page 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Page 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Page 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Page 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Page 148: ...22 MUY GE18NA 1 OBH549G ...
Page 149: ...23 MUZ GE24NA OBH549G ...
Page 150: ...24 MUY GE24NA OBH549G ...
Page 199: ...73 OBH549G ...