18
EMERGENCY OPERATION switch
E.O.
SW
E.O.
SW
8-9. EMERGENCY/TEST OPERATION
In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor
unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote
controller run down. The unit will start and OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at
High speed and the temperature control does not work.
After 30 minutes of test run operation the system shifts to EMERGENCY COOL/HEAT MODE with a set temperature of
75°F (24°C). The fan speed shifts to Med.
The coil frost prevention works even in the test run or the emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode.
Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any
signal from the remote controller. In case of latter normal operation will start.
NOTE
: Do not press EMERGENCY OPERATION switch during normal operation.
8-11. CHANGING TEMPERATURE INDICATION (°F /°C)
8-10. 3-MINUTE TIME DELAY OPERATION
When the system turns OFF, compressor will not restart for 3 minutes as 3-minute time delay function operates to protect
compressor from overload.
The preset unit is °F.
°F
→
°C : Press RESET button while the
temperature buttons are pressed.
°C
→
°F : Press RESET button or remove
the batteries.
•
•
•
Press RESET button gently using
a thin instrument.
Operation mode
COOL
HEAT
(MUZ)
Set temperature
75°F (24°C)
75°F (24°C)
Fan speed
Med.
Med.
Horizontal vane
Auto
Auto
The operation mode is indicated by the Operation
Indicator lamp as following
Operation Indicator lamp
(MSZ type)
EMERGENCY COOL
↓
EMERGENCY HEAT
↓
STOP
(MSY type)
EMERGENCY COOL
↓
STOP
Lighted
Not
lighted
Summary of Contents for Mr.Slim MSY-D30NA
Page 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Page 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Page 43: ...9 MUY D30NA MUY D36NA ...
Page 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Page 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Page 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Page 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Page 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Page 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Page 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Page 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Page 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Page 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Page 148: ...22 MUY GE18NA 1 OBH549G ...
Page 149: ...23 MUZ GE24NA OBH549G ...
Page 150: ...24 MUY GE24NA OBH549G ...
Page 199: ...73 OBH549G ...