22
9-3. INSTRUCTION OF TROUBLESHOOTING
Indoor unit oper-
ates.
Outdoor unit
does not operate.
If blinking of OPERATION INDI-
CATOR lamp cannot be checked,
it can be checked with failure
mode recall function.
Indoor unit operates.
Outdoor unit does
not operate normally.
Indoor unit does
not receive the
signal from re-
mote controller.
OPERATION INDICATOR
lamp on the indoor unit is
fl
ashing on and off.
Outdoor unit
operates only
in Test Run
operation.
Outdoor unit
does not
operate even
in Test Run
operation.
Unit does not
operate normal
operation in
COOL or HEAT
mode.
Indoor unit
operates, when
EMERGENCY
OPERATION
switch is pressed.
Indoor unit does
not operate, when
EMERGENCY
OPERATION
switch is pressed.
Check room
temperature
thermistor.
Refer to 8-7.
"Test point
diagram and
voltage".
Refer to "How
to check
inverter/com-
pressor".
Refer to
"Check of R.V.
coil".
Refer to 9-6.
"Check of remote
controller and
receiver P.C.
board".
1. Check indoor/out-
door connecting wire.
(Check if the power is
supplied to the indoor
unit.)
2. Refer to 9-6. "Check
of indoor electronic
control P.C. board and
indoor fan motor".
Left lamp
Flash on and
off at 0.5-sec-
ond intervals
Cause:
Indoor/Outdoor
unit
• Miswiring or
trouble of
serial signal
Left lamp
2-time
fl
ash
Cause:
Indoor unit
• Trouble of
room tem-
perature /
indoor coil
thermistor
Left lamp
3-time
fl
ash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
Left lamp
4-time
fl
ash
Cause:
Indoor unit
• Trouble
of indoor
unit control
system
Left lamp
5-time
fl
ash
Cause:
Outdoor unit
• Outdoor
power
system
abnormality
Left lamp
6-time
fl
ash
Cause:
Outdoor unit
• Trouble of
thermistor in
outdoor unit
Left lamp
7-time
fl
ash
Cause:
Outdoor unit
• Trouble of
outdoor con-
trol system
Left lamp
14-time
fl
ash
Cause:
Outdoor unit
• Other ab-
normality
Start
Refer to 9-6.
"How to
check miswir-
ing and serial
signal error".
Check room
temperature
thermistor
and indoor
coil thermis-
tor. Refer
to 9-7."Test
point diagram
and voltage".
Refer to 9-6.
"Check of
indoor fan
motor".
Replace the
indoor elec-
tronic control
P.C. board.
Refer to "How
to check
inverter/com-
pressor".
Refer to
"Check of
outdoor
thermistors".
Check "Flow
chart of the
detailed
outdoor unit
failure mode
recall func-
tion."
"Test Run operation" means the
operation within 30 minutes after
EMERGENCY OPERATION
switch is pressed.
Refer to outdoor unit service manual.
Replace the
inverter P.C.
board or the
outdoor elec-
tronic control
P.C. board.
Summary of Contents for Mr.Slim MSY-D30NA
Page 41: ...7 MUZ D30NA MUZ D30NA U1 MUZ D36NA MUZ D36NA U1 5 WIRING DIAGRAM ...
Page 42: ...8 MUZ D30NA 1 MUZ D30NA U2 MUZ D36NA 1 MUZ D36NA U2 ...
Page 43: ...9 MUY D30NA MUY D36NA ...
Page 44: ...10 MUY D30NA 1 MUY D36NA 1 ...
Page 139: ...13 MUZ GE09NA MUZ GE12NA 5 WIRING DIAGRAM MUZ GE09NA2 MUZ GE12NA2 OBH549G ...
Page 140: ...14 MUZ GE09NAH MUZ GE12NAH MUZ GE09NAH2 MUZ GE12NAH2 OBH549G ...
Page 141: ...15 MUY GE09NA MUY GE12NA MUY GE09NA2 MUY GE12NA2 OBH549G ...
Page 142: ...16 MUZ GE15NA 1 MUZ GE15NA OBH549G ...
Page 143: ...17 MUZ GE15NAH MUZ GE15NA2 OBH549G ...
Page 144: ...18 MUY GE15NA MUZ GE15NAH2 OBH549G ...
Page 145: ...19 MUY GE15NA 1 MUY GE15NA2 OBH549G ...
Page 146: ...20 MUZ GE18NA MUZ GE18NA 1 OBH549G ...
Page 147: ...21 MUZ GE18NAH MUY GE18NA OBH549G ...
Page 148: ...22 MUY GE18NA 1 OBH549G ...
Page 149: ...23 MUZ GE24NA OBH549G ...
Page 150: ...24 MUY GE24NA OBH549G ...
Page 199: ...73 OBH549G ...