Appendix 7 Processing Time
Master station and local stations
■
Master station (RX)
Local station (RY)
Shows the time after the local station CPU module device is turned on or off until the master station CPU module device is
turned on or off.
(m = 1)
(m = 2 to 4)
SM: Master station sequence scan time
LS: Link scan time
SL: Local station sequence scan time
n: (LS
m)
SL (Round up the calculated value to the nearest integer.)
n1: SM
LS (Round up the calculated value to the nearest integer.)
k: SL
(LS
m) (Round up the calculated value to the nearest integer.)
m: Constant of "RWw/RWr Setting" set for the local station in "Network Configuration Settings" of "Basic Settings"
■
Master station (RY)
Local station (RX)
Shows the time after the master station CPU module device is turned on or off until the local station CPU module device is
turned on or off.
SM: Master station sequence scan time
LS: Link scan time
SL: Local station sequence scan time
n3: SL
LS (Round up the calculated value to the nearest integer.)
Calculation
value
Station-based block data assurance
No station-based block data assurance
Asynchronous with
sequence scan
Synchronous with
sequence scan
Asynchronous with
sequence scan
Synchronous with
sequence scan
Normal value
(SM
1) + (LS
k) + (SL
1)
(SM
1) + (LS
1) + (SL
1)
(SM
1) + (LS
1) + (SL
1)
(SM
1) + (LS
1) + (SL
1)
Maximum
value
(SM
1) + (LS
(k + n1)) + (SL
1)
(SM
1) + (LS
k) + (SL
1)
(SM
1) + (LS
2) + (SL
1)
(SM
1) + (LS
k) + (SL
1)
Calculation
value
Station-based block data assurance
No station-based block data assurance
Asynchronous with
sequence scan
Synchronous with
sequence scan
Asynchronous with
sequence scan
Synchronous with
sequence scan
Normal value
(SM
1) + (LS
m
k) + (SL
n)
(SM
1) + (LS
m) + (SL
n)
(SM
1) + (LS
m) + (SL
n)
(SM
1) + (LS
m) + (SL
n)
Maximum
value
(SM
1) + (LS
m
(k + n1)) +
(SL
(n + 1))
(SM
1) + (LS
m
2) + (SL
(n + 1))
(SM
1) + (LS
(n1 + 1)) + (SL
2)
(SM
1) + (LS
m
2) + (SL
2)
Item
Number of points in "RWw/RWr Setting"
0 to 256 words
257 to 512 words
513 to 768 words
769 to 1024 words
m
1
2
3
4
Calculation
value
Station-based block data assurance
No station-based block data assurance
Asynchronous with
sequence scan
Synchronous with
sequence scan
Asynchronous with
sequence scan
Synchronous with
sequence scan
Normal value
(SM
1) + (LS
n3) + (SL
1)
(SM
1) + (LS
1) + (SL
2)
(SM
1) + (LS
1) + (SL
1)
(SM
1) + (LS
1) + (SL
1)
Maximum
value
(SM
1) + (LS
(n3 + 1)) + (SL
2)
(SM
1) + (LS
2) + (SL
2)
(SM
1) + (LS
2) + (SL
2)
(SM
1) + (LS
2) + (SL
2)