3 PROGRAMMING
3.3 Communication Example of Safety Communication Function
183
3
8.
Set the safety communication setting as follows.
[Navigation window]
[Parameter]
[Module Information]
[RJ71GF11-T2]
[Application Settings]
[Safety
Communication Setting]
[Safety Communication Setting]
9.
Log on to the programmable controller.
[Online]
[User Authentication]
[Log on to PLC]
• If logon cannot be performed, writing user information or initializing all information of the programmable controller is
required. (
GX Works3 Operating Manual)
10.
Write the set parameters to the Safety CPU on the local station.
[Online]
[Write to PLC]
11.
Visually check if the safety communication setting is correctly written after writing parameters. For how to check the
parameters, refer to the following.
GX Works3 Operating Manual
In this example, default values were used for parameters that are not shown above. For the parameter setting,
refer to the chapter explaining the parameters in this manual. (