4 TROUBLESHOOTING
4.5 List of Error Codes
271
4
D2AFH
The own station number was specified as the target
station number of transient transmission.
• Transient data transmission addressed to the own
station was requested. Check the network number
and target station number, and retry the operation.
• Check if "Routing Setting" of "CPU Parameter" is
correctly set, and take action.
D2B0H
Transient transmission failed.
• Check if the switching hub and the cables at the
request source are connected properly.
• Connect the cable to the other port on the request
source, and retry the operation.
• Lower the transient transmission usage frequency,
and then perform again.
D2B1H
The receive queue is full.
• Pause the transient transmission temporarily, and
retry the operation.
• Lower the transient transmission usage frequency,
and then perform again.
• Use the COM instruction to increase the frequency
of transient transmission.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D2E0H
During execution of the IP communication test, the test
was retried.
Retry the IP communication test after a while. (Up to
four IP communication tests can be simultaneously
executed.)
D2E1H
The IP communication test was completed with an
error (no response to ping).
• Check "Communication Target" of the IP
communication test.
• Check and correct the status of the cable
connection and line between the CC-Link IE Field
Network gateway setting station and the
communication destination.
• Enable a response to the ping command (ICMP
echo request) in the firewall settings on the personal
computer or antivirus software.
D602H
Parameter error
• Write the network parameter to the CPU module
again.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D605H
Parameter error
• Write the network parameter to the CPU module
again.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D611H
Parameter error (each station device range
assignment error (RWw))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the size of the slave
station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D612H
Parameter error (each station device range
assignment error (RWw))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the offset of the slave
station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D613H
Parameter error (each station device range
assignment error (RWr))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the size of the slave
station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D614H
Parameter error (each station device range
assignment error (RWr))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the offset of the slave
station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
Error
code
Error details and causes
Action
Detailed Information