4 TROUBLESHOOTING
4.5 List of Error Codes
D615H
Parameter error (each station device range
assignment error (RY))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the size of the slave
station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D616H
Parameter error (each station device range
assignment error (RY))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the offset of the slave
station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D617H
Parameter error (each station device range
assignment error (RX))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the size of the slave
station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D618H
Parameter error (each station device range
assignment error (RX))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the offset of the slave
station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D619H
Parameter error
• Write the network parameter to the CPU module
again.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61AH
Parameter error
• Write the network parameter to the CPU module
again.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61BH
Parameter error (device overlap error (RWw))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the offset or size of
the slave station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61CH
Parameter error (device overlap error (RWr))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the offset or size of
the slave station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61DH
Parameter error (device overlap error (RY))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the offset or size of
the slave station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61EH
Parameter error (device overlap error (RX))
• Write the network parameter to the CPU module
again.
• Execute again after correcting the offset or size of
the slave station link device in the setting data.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
D61FH
Parameter setting by the CCPASET instruction has
failed.
Execute again after setting "Setting Method of Basic/
Application Settings" under "Parameter Setting
Method" in "Required Settings" to "Program".
D620H
The transient data is incorrect.
• Correct the transient data at the request source,
and retry the operation.
• If the error occurs again even after taking the above,
please consult your local Mitsubishi representative.
Error
code
Error details and causes
Action
Detailed Information