2 PARAMETER SETTINGS
2.4 Application Settings
151
2
If the transfer target network module is on a network other than CC-Link IE Field Network, set the transfer
target link devices within the own station send range of the network module. If the link devices are set within
the send range of another station, the transferred data are overwritten with the send data of another station.
Safety Communication Setting
Set whether to use the safety communication function or not and set safety connections.
Set the following items before configuring the safety communication setting.
• "Network Configuration Settings" in "Basic Settings" (
Page 129 Network Configuration Settings)
• "Parameter Processing of Slave Station" in "Network Configuration Settings" under "Basic Settings" (
User's manual for the slave station used)
If the above items are not set, the slave station is not displayed as the target module in "Select the target
module for the Safety Communication Setting" window and safety communications cannot be set.
Item
Description
Setting range
To Use or Not to Use the Safety Communication
Setting
Set whether to use the safety communication
function or not.
• Use
• Not Use
(Default: Not Use)
Safety Communication Setting
Set the safety connections and transfer ranges of
safety devices required for safety communications.
0
1000
0
LB
RX
Set this within its own
station send range of
the network module.
Own station send range
Other station send range
Master station
(station No.0)
Network module
1000 to 103F
0 to 3F