FX2N-2LC Temperature Control Block
Buffer Memory (BFM) 7
7-21
7
7.2.32
In BFM #50, set the loop breaking alarm dead zone of CH1.
In BFM #69, set the loop breaking alarm dead zone of CH2.
The loop breaking alarm function may issue alarms caused by disturbances (effect of another
heat source, etc.) even if there is no abnormality in the control system. In order to prevent
such alarms, by setting the loop breaking alarm dead zone, the region in which the alarm func-
tion is disabled (non-alarm status region) can be set.
For example, if the loop breaking alarm dead zone is set to "10
°
C", 10
°
C above the set value
(SV) and 10
°
C below the set value (SV) are treated as the non-alarm status region (width of 20
°
C in total).
While the measured value (PV) is located within the non-alarm region, alarm is not issued
even if the alarm condition is satisfied.
The allowable set range is form 0.0 (or 0) to the input range span (
°
C or
°
F).
When BFM #50 / #69 is set to "0", the loop breaking alarm dead zone function is disabled.
*1 While the temperature is rising: Alarm status region
While the temperature is decreasing: Non-alarm status region
*2 While the temperature is rising: Non-alarm status region
While the temperature is decreasing: Alarm status region
*3 LBD operation gap (0.01%FS)
Alarm status region
Alarm status region
LBD operation gap *3
LBD operation gap *3
Non-alarm status region
Low
High
Temperature set value (SV) LBD set value
*1
*2
Summary of Contents for MELSEC FX2N-2LC
Page 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Page 4: ...FX2N 2LC Tempereture Control Block ii ...
Page 6: ...FX2N 2LC Tempereture Control Block iv ...
Page 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Page 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Page 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Page 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Page 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Page 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Page 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Page 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Page 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Page 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Page 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Page 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Page 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Page 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...