FX2N-2LC Temperature Control Block
Alarm 6
6-5
6
Alarm wait operation
The wait operation ignores the alarm status of the measured value (PV) occurred when the
power is turned on, and disables the alarm function until the measured value (PV) goes out of
the alarm status once.
When control starts, the wait operation is performed also.
Alarm re-wait operation
The alarm re-wait operation ignores the alarm status of the measured value (PV) occurred
when the power is turned on, and disables the alarm function until the measured value (PV)
goes out of the alarm status once.
When the temperature set value (SV) is changed, the measured value (PV) for deviation alarm
changes accordingly. At this time, even if the measured value (PV) becomes the alarm status,
the alarm re-wait function ignores it again and disables the alarm function until the measured
value (PV) goes out of the alarm status again.
Alarm
status
Non-alarm
status
Alarm set
value
Measured value (PV)
Alarm status
Devia
tion
Measured value
(PV)
Temperature
set value (SV)
< When the wait operation is performed >
Time
< When the wait operation is not performed >
Wait operation region
Alarm set
value
Measured value (PV)
Alarm status
Devia
tion
Measured value
(PV)
Temperature
set value (SV)
Time
Time
Measured value (PV)
Re-wait operation
Alarm status
Alarm status
Non-alarm
status
Alarm set value
Temperature set
value (SV1)
Temperature set
value (SV)
Deviation
Deviation
Wait operation region
Set value is changed.
Measured value (PV)
Wait operation region
Alarm set value
Summary of Contents for MELSEC FX2N-2LC
Page 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Page 4: ...FX2N 2LC Tempereture Control Block ii ...
Page 6: ...FX2N 2LC Tempereture Control Block iv ...
Page 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Page 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Page 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Page 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Page 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Page 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Page 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Page 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Page 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Page 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Page 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Page 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Page 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Page 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...