FX2N-2LC Temperature Control Block
Buffer Memory (BFM) 7
7-4
7.2
Details of buffer memories
7.2.1
BFM #0: Flag
Operation of b15 (Temperature control ready flag)
Description on operation
1) When the power is turned on and initialization of the temperature control CPU is com-
pleted, the temperature control ready flag turns on.
2) While the temperature control ready flag is ON, the FX
2N
-2LC accepts TO instructions.
Table 7.2:
Bit No.
Description
Operation
b0
Error present
Turns on when an error among b1 to b10 below has
occurred.
b1
Set value range error
Turns on when data outside set range is written.
b2
24 VDC power supply error
Turns on when driving power supply (24 VDC) is not sup-
plied.
b3
Set value backup error
Turns on when an error has been caused by noise or when
a failure has occurred in FX
2N
-2LC.
If contents of error are not eliminated even after power is
turned off once then on again, contact Mitsubishi Electric
System Service.
b4
Not used
---
b5
Not used
---
b6
Not used
---
b7
Not used
---
b8
Sum check error for adjustment
data error
Turns on when an error has been caused by noise or when
a failure has occurred in FX
2N
-2LC.
If contents of error are not eliminated even after power is
turned off once then on again, contact Mitsubishi Electric
System Service.
b9
Cold contact temperature com-
pensation data error
b10
A/D converted value error
b11
Not used
---
b12
Controlling flag
Turns on when FX
2N
-2LC is performing control.
b13
Set value being backed up
Remains ON while set values are being backed up.
Refer to 7.2.42.
b14
Initialization completion flag
Turns on when initialization is completed.
b15
Temperature control ready flag
Turns on when FX
2N
-2LC becomes ready for operation.
Temperature control ready flag
Initialization of temperature
control CPU is completed.
Power is turned on.
It takes 500 ms
maximum.
Summary of Contents for MELSEC FX2N-2LC
Page 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Page 4: ...FX2N 2LC Tempereture Control Block ii ...
Page 6: ...FX2N 2LC Tempereture Control Block iv ...
Page 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Page 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Page 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Page 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Page 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Page 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Page 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Page 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Page 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Page 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Page 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Page 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Page 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Page 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...