FX2N-2LC Temperature Control Block
Buffer Memory (BFM) 7
7-28
7.2.40
BFM #81: CT monitor method changeover
In BFM #81, change over the CT monitor method. This setting is applied to both CH1 and CH2.
The current is detected by sampling performed every second.
While the temperature is controlled, the control output repeatedly turns on and off. Accord-
ingly, the current in the ON time (= ON current) and the current in the OFF time (= OFF current)
are alternately displayed. If the output cycle is short, the displayed value is not stable and is
difficult to read.
To cope with this, the display (monitor) method can be selected.
When BFM #81 is set to "K0 (initial value)", the ON current and the OFF current are alternately
displayed.
When BFM #81 is set to "K1", only the ON current is displayed. Even in the OFF time, the ON
current remains displayed.
When control is stopped, the OFF current is displayed without regard to the setting of BFM
#81.
7.2.41
BFM #82: Set value range error address
When an out-of-range error occurs in the set value written to each BFM, BFM #82 indicates
the BFM No. in which the error occurs.
While no error occurs, BFM #82 stores "0".
When an error occurs, BFM #82 stores the BFM No. in which the error occurs. Check the set
range, set a proper value for the corresponding BFM, then reset the error (BFM #10).
Summary of Contents for MELSEC FX2N-2LC
Page 1: ...USER S MANUAL FX2N 2LC Temperature Control Block ...
Page 4: ...FX2N 2LC Tempereture Control Block ii ...
Page 6: ...FX2N 2LC Tempereture Control Block iv ...
Page 12: ...FX2N 2LC Temperature Control Block Introduction 1 ...
Page 16: ...FX2N 2LC Temperature Control Block Product Configuration 2 ...
Page 22: ...FX2N 2LC Temperature Control Block Specifications 3 ...
Page 28: ...FX2N 2LC Temperature Control Block Specifications 3 3 6 ...
Page 30: ...FX2N 2LC Temperature Control Block Wiring 4 ...
Page 34: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 ...
Page 44: ...FX2N 2LC Temperature Control Block Introduction of Functions 5 5 10 ...
Page 46: ...FX2N 2LC Temperature Control Block Alarm 6 ...
Page 52: ...FX2N 2LC Temperature Control Block Alarm 6 6 6 ...
Page 54: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 ...
Page 84: ...FX2N 2LC Temperature Control Block Buffer Memory BFM 7 7 30 ...
Page 86: ...FX2N 2LC Temperature Control Block Program Example 8 ...
Page 94: ...FX2N 2LC Temperature Control Block Program Example 8 8 8 ...
Page 96: ...FX2N 2LC Temperature Control Block Troubleshooting 9 ...