4.9
FAN
By accessing the masks of the pLDPRO interface on board of the unit using the Service password, it is possible to obtain information on the status
of the fan, the condensation or evaporation pressure, and the regulation percentage.
4.9.1
EVAPORATION CONTROL
The fan is managed to control the evaporation based on the pressure, in accordance with the following function:
Pressure
100%
Cut-Off
(1422)
Forcing setpoint
(1421)
Speed
High Speed
(131P)
Min Speed
(131N)
Forcing
(1420)
Prop. band
(1419)
Setpoint (1418)
4.9.2
CONDENSATION CONTROL
As far as condensation control, i-BX(-N) units have double fan management, in Cooling Mode for i-BX units and in chiller operation for i-BX-N units.
In addition to fan regulation based on the condensation pressure, in chiller operation it is also possible to have regulation based on the external
temperature (alternative to pressure regulation).
4.9.2.1
Regulation based on pressure
Pressure
100%
Cut-Off
(1415)
Speed
High Speed
(131T)
Min Speed
(131R)
Forcing
(1417)
Prop. band
(1414)
Setpoint
(1413)
Forcing setpoint
(1416)