2.3
AMBIENT THERMOSTAT
The interface that can be used with zone control (accessory) is an
N-THC
graphic display.
The N-THC interface
is used for zone control and is specific for i-BX-N units. The N-THC thermostat for i-BX-N units requires 230 Volt power supply.
By connecting two N-THC in series to connector 4 (see chapter HARDWARE) of the controller and using the Modbus protocol it is possible to control
2 zones (1 high temperature and 1 low temperature zone). Control of each individual system zone will be possible through this interface.
Dimensions
Connections
2.3.1
AMBIENT THERMOSTAT ADDRESSING PROCEDURE
1
Initial display
2
Press at the same time for
3 seconds keys +
3
Rotate the knob and select the user
password: 22
4
Press the knob to confirm the password
5
Press the knob
6
In succession:
A
Rotate the knob to select the value
B
Press the knob to confirm