2.4.14
MENU 14
Part n.
Description
Default
Unit
Min.
Max.
P1402
System flow switch alarm dalay time at pump start
15
s
0
999
P1403
Alarm delay time System flow switch in steady operating
0
s
0
999
P1404
Reset system flow switch (0=Auto; 1=Manual)
0
-
0
1
P1405
Pump stop time after warning
10
s
1
999
P1406
Condensing fan control mode - 0: Condensing Pressure; 1: External Temperature
1
-
0
1
P1407
Condensing fan setpoint for High Speed activation in External Temperature control mode
10.0
°C
-999.9
999.9
P1408
Condensing fan setpoint for fan at 100% activation in External Temperature control mode
20.0
°C
-999.9
999.9
P1409
Condensing fan deactivation differential (to pass to the previous step) in External Temperature
control mode
2.0
°C
-99.9
99.9
P1410
Low temperature setpoint limit Sanitary
35.0
°C
0
999.9
P1412
Max limit temperature DHW
85.0
°C
-999.9
999.9
P1413
Condensation set
29.6
Bar
-3276.8
3276.7
P1414
Condensation reg. Prop. Band
0.3
Bar
0
99.9
P1415
Condensation reg. Cut off
0.1
Bar
0
9.9
P1416
Condensation reg. Set force
30.0
Bar
0
999.9
P1417
Condensation reg. Max speed
0.1
Bar
0
9.9
P1418
Evaporation set
11.5
Bar
-1.0
99.9
P1419
Evaporation reg. Prop. Band
3.0
Bar
0
99.9
P1420
Evaporation reg. Max speed
1.0
Bar
0
9.9
P1421
Evaporation reg. Set force
7.5
Bar
0
999.9
P1422
Evaportaion reg. Cut off
1.0
Bar
0
9.9
P1423
Type of plant pump (0: Adjustable; 1: Fix speed)
0
-
0
1
P1424
Enable sleep mode (0:NO; 1:YES)
0
-
0
1
P1425
Day start function
1
d
1
31
P1426
Month start function
1
min
1
12
P1427
Year start function
0
y
0
99
P1428
Hour start function
0
h
0
23
P1429
Active function (0:NO; 1:YES)
0
-
0
1
P1430
Geothermal flow switch alarm dalay time at pump start
15
s
0
999
P1431
Alarm delay time geothermal flow switch in steady operating
5
s
0
999
P1432
Reset geo flow switch (0=Auto; 1=Manual)
0
-
0
1
P1433
Pump geo stop time after warning
90
s
1
999
P1434
Pressure threshold to increase fan speed (only in summer with external temperature regulation)
30.0
Bar
0
999.9
P1435
Pressure threshold to decrease fan speed (only in summer with external temperature regulation)
3.0
Bar
0
999.9
P1436
Condensing fan setpoint for Minimum Speed activation in External Temperature control mode
0.0
°C
-999.9
999.9