10
Option
a
n
d
Pe
rip
h
e
ral
Device
s
29
Name (Model)
Specifications, Structure, etc.
DIN rail mounting
attachments
FR-UDA[]
●
Attachment to enable installation of FR-CS80 series on DIN rail.
●
Approximate dimension
FR-UDA01
FR-UDA02
EMC Directive compliant
EMC filter
SF
FR-E5NF-H[]K
(400V class)
FR-S5NFSA-[]K
(200V class)
●
The EMC compliant EMC filter (EN61800-3 2nd Environment Category C3) is a filter compliant with the EU EMC Directive
(EN61800-3 2nd Environment Category C3).
●
Selection table
Attachment Model
Inverter Capacity
FR-CS84
FR-CS82S
FR-UDA01
012, 022
025, 042
FR-UDA02
036, 050, 080
070, 100
108
67
68
67
128
128
4-M4 0.7 screw
8.7
3-M4 0.7 screw
Hook
Hook
15
15
10
8.7
(Unit: mm)
∗1
Depth is 12mm deeper when an intercompatibility attachment is installed.
∗2
Leakage current for one phase of three-phase three-wire star-connection power supply.
Leakage current for all phases of three-phase three-wire delta-connection power supply is
three times greater than the indicated value.
(Note) This is a sample outline dimension drawing. The shape differs by the model.
●
Prevention of leakage current
Take the following actions to prevent malfunction of peripheral devices or an electric shock caused by leakage current.
1) Earth (ground) the EMC filter before connecting the power supply. When doing so, confirm that earthing (grounding) is
securely performed through the earthing (grounding) part of the enclosure.
2) Select an appropriate earth leakage circuit breaker or an earth leakage relay by considering leakage current of the EMC filter.
Note that earth leakage circuit breaker may not be used in some cases such as when leakage current of the EMC filter is too
large. In that case, use an earth leakage relay with high sensitivity. When both of earth leakage circuit breaker and earth
leakage relay cannot be used, securely earth (ground) as explained in 1).
EMC filter Model
Applicable inverter
model
Outline
dimension
(Unit: mm)
Mass
(kg)
Leakage
current
(mA)
∗2
(reference
value)
Loss
(W)
W
H
D
SF1306
FR-CS82S-025, 042
110
200
36.5
0.7
10
7.3
FR-E5NF-H3.7K
FR-CS84-012 to 080
140
210
46
1.2
44.5
8
FR-E5NF-H7.5K
FR-CS84-120, 160
220
210
47
2
68.4
15
FR-S5NFSA-1.5K FR-CS82S-070, 100
110
168
47
0.7
9.5
11
EMC filter
Model
Applicable
inverter model
Intercompatibility
attachment
∗1
Outline dimension
(Unit: mm)
Mass
(kg)
Leakage
current
(mA)
∗2
(reference
value)
Loss
(W)
W
H
D
D1
SF1175
FR-CS84-230,
295
FR-AAT02
253 530 60
35 4.7
76
56
W
H
D
W
H
D
D1
Summary of Contents for FREQROL-CS80
Page 1: ...COMPACT SMART INVERTER FREQROL CS80 FACTORY AUTOMATION ...
Page 36: ...36 ...
Page 37: ...37 ...