Para
meter
list
8
22
Se
co
nd
fu
nc
tio
n
44
F020
Second acceleration/deceleration time
0 to 3600 s
0.1 s
5 s
10 s
15 s
45
F021
Second deceleration time
0 to 3600 s, 9999
0.1 s
9999
Autom
atic
rest
ar
t
57
A702
Restart coasting time
0, 0.1 to 5 s, 9999
0.1 s
9999
58
A703
Restart cushion time
0 to 60 s
0.1 s
1 s
—
59
F101
Remote function selection
0 to 3
1
0
—
60
G030
Energy saving control selection
0, 9
1
0
—
65
H300
Retry selection
0 to 5
1
0
—
66
H611
Stall prevention operation reduction starting
frequency
0 to 400 Hz
0.01 Hz
50 Hz
Re
try
67
H301
Number of retries at fault occurrence
0 to 10, 101 to 110
1
0
68
H302
Retry waiting time
0.1 to 600 s
0.1 s
1 s
69
H303
Retry count display erase
0
1
0
—
71
C100
Applied motor
0 to 2
1
0
—
72
E600
PWM frequency selection
2 to 12
1
2
—
73
T000
Analog input selection
0, 1, 10, 11
1
1
—
74
T002
Input filter time constant
0 to 8
1
1
—
75
—
Reset selection/disconnected PU detection/
PU stop selection
0 to 3, 14 to 17
1
14
E100
Reset selection
0, 1
0
E101
Disconnected PU detection
E102
PU stop selection
1
—
77
E400
Parameter write selection
0 to 2
1
2
—
78
D020
Reverse rotation prevention selection
0 to 2
1
0
—
79
D000
Operation mode selection
0 to 4
1
0
Mot
o
r
co
nst
ant
80
C101
Motor capacity
0.2 to 15 kW, 9999
0.01 kW
9999
82
C125
Motor excitation current
0 to 500 A, 9999
0.01 A
9999
90
C120
Motor constant (R1)
0 to 50
Ω
, 9999
0.001
Ω
9999
96
C110
Auto tuning setting/status
0, 1
1
0
Adju
st
able
3 point
s V/
F
100
G040
V/F1 (first frequency)
0 to 400 Hz, 9999
0.01 Hz
9999
101
G041
V/F1 (first frequency voltage)
0 to 1000 V
0.1 V
0 V
102
G042
V/F2 (second frequency)
0 to 400 Hz, 9999
0.01 Hz
9999
103
G043
V/F2 (second frequency voltage)
0 to 1000 V
0.1 V
0 V
104
G044
V/F3 (third frequency)
0 to 400 Hz, 9999
0.01 Hz
9999
105
G045
V/F3 (third frequency voltage)
0 to 1000 V
0.1 V
0 V
PU conne
ct
or communi
ca
tio
n
117
N020
PU communication station number
0 to 31(0 to 247)
1
0
118
N021
PU communication speed
48, 96, 192, 384, 576,
768, 1152
1
192
119
—
PU communication stop bit length / data
length
0, 1, 10, 11
1
1
N022
PU communication data length
0, 1
0
N023
PU communication stop bit length
0, 1
1
120
N024
PU communication parity check
0 to 2
1
2
121
N025
PU communication retry count
0 to 10, 9999
1
1
122
N026
PU communication check time interval
0, 0.1 to 999.8 s, 9999
0.1 s
0
123
N027
PU communication waiting time setting
0 to 150 ms, 9999
1 ms
9999
124
N028
PU communication CR/LF selection
0 to 2
1
1
—
125
T022
Terminal 2 frequency setting gain frequency
0 to 400 Hz
0.01 Hz
50 Hz
—
126
T042
Terminal 4 frequency setting gain frequency
0 to 400 Hz
0.01 Hz
50 Hz
P
ID oper
ati
o
n
127
A612
PID control automatic switchover frequency
0 to 400 Hz, 9999
0.01 Hz
9999
128
A610
PID action selection
0, 20, 21
1
0
129
A613
PID proportional band
0.1 to 1000%, 9999
0.1%
100%
130
A614
PID integral time
0.1 to 3600 s, 9999
0.1 s
1 s
131
A601
PID upper limit
0 to 100%, 9999
0.1%
9999
132
A602
PID lower limit
0 to 100%, 9999
0.1%
9999
133
A611
PID action set point
0 to 100%, 9999
0.01%
9999
134
A615
PID differential time
0.01 to 10 s, 9999
0.01 s
9999
PU
145
E103
PU display language selection
0 to 7
1
1
Cu
rrent
det
ectio
n
150
M460
Output current detection level
0 to 200%
0.1%
150%
151
M461
Output current detection signal delay time
0 to 10 s
0.1 s
0 s
—
156
H501
Stall prevention operation selection
0 to 31, 100, 101
1
0
—
157
M430
OL signal output timer
0 to 25 s, 9999
0.1 s
0 s
Function
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increment
Initial
value
Customer
setting