18
Device map
S
pe
ci
al
r
e
gi
st
er
s f
or
c
ont
ro
l
D9136
Error history 1, 2
Stores the errors that occurred in the inverter in order
of occurrence.
24
D9137
Error history 3, 4
D9138
Error history 5, 6
D9139
Error history 7, 8
D9140
Operation mode
setting read
Stores the current operation mode.
27
D9141
Set frequency
read (RAM)
Reads and stores the set frequency (RAM).
28
D9142
Set frequency
read (EEPROM)
Reads and stores the set frequency (EEPROM).
28
D9143
Operation mode
setting write
Sets a new operation mode.
30
D9144
Set frequency
write (RAM)
Sets the running frequency (RAM).
31
D9145
Set frequency
write (EEPROM)
Sets the running frequency (EEPROM).
32
D9146
Faults history
batch clear
Write H9696 to clear the faults history.
33
D9147
Parameter clear
H9696 write: Parameter clear
H9966 write: All clear
H5A5A write:Parameter clear except communication
parameters
H55AA write:All clear except communication
parameters
During GX Developer communication, perform
clearing by H5A5A or H55AA.
34
D9148
Inverter operation
status control
Turn on/off the corresponding bits to control the
inverter operation status.
The initial value: All "0". When M9255 is off, this
device does not function.
35
D9149
Inverter operation
status control
enable/disable
setting
Enable/disable the inverter operation status control
using D9148 and M9200 to M9211 by turning on/off
the corresponding bits.
Bit image is the same as D9148.
The initial value: All "0" (invalid)
The SQ signal can be input from external terminals at
any time. (The SQ signal cannot be controlled with
bits from D9149.)
36
Number
Name
Description
Page
B15
B12B11
B8B7
B4B3
B0
0:OFF
1:ON
STF
STR
RH
RM
RL
JOG
RT
AU
CS
MRS
STOP
RES
Invalid
Summary of Contents for FR - F700
Page 1: ...INVERTER FR F700 FR F 700 INVERTER PLC FUNCTION PROGRAMMING MANUAL ...
Page 7: ...VI MEMO ...
Page 131: ...124 Sequence instructions Program Examples LD LDI AND ANI OR ORI ORB ANB Coding Coding Coding ...
Page 207: ...200 MEMO ...
Page 211: ...204 MEMO ...
Page 212: ...205 APPENDIX Appendix 1 Instruction processing time 206 ...
Page 216: ...FR F 700 INVERTER ...