101
Self-diagnostic function
3
SEQUENCE PROGRA
M
M
ING
3.16.1 Error-time operation mode
The built-in PLC function allows you to set whether the sequence program operation
will be stopped or continued at occurrence of an operation error.
Use the built-in PLC function parameter to set whether operation will be stopped or
continued.
z
Default value of error-time operation mode
The following table indicates the default value (initial value) of the error-time
operation mode and the status of the built-in PLC function.
Table 3.5 Error-time Operation Mode
Error Definition
CPU Status
Operation
P.RUN
LED
Special
relays
turned on
Special
registers
for data
storage
Self-
diagnostic
error No.
(D9008)
Default value
Operation
error
An error occurred in
the sequence
program, e.g. an
attempt was made to
make BCD
conversion of any
value outside the
range 0 to 9999 (or 0
to 99999999).
Continuation
On
M9010
M9011
D9010
D9011
50