4
3
1.Features
Easy and Low-Cost Measurement
1
■Simple Measurement/Installation
The built-in LCD screen enables the settings, measurements, and displays required for
measuring energy with a single unit.
■Product Lineup that Provides Easy Equipment Selection
This measuring unit lineup consists of a "High Performance Model" and a "Standard Model".
①
High Performance Model: For customers who want to perform harmonic measurements, alarm monitoring,
upper/lower limits monitoring, alarm output and pulse input/output, in addition to the Standard Model features
②
Standard Model: For customers who "want to start measuring energy in a simple and low-cost manner".
■Specialized Cable is Not Required
You can use a general-purpose cable between the measuring unit and split current sensor!
Cost can be reduced because no specialized cable is required.
* EMU2-CB-Q5B(-4W) is necessary if using a split 5A current sensor.
* Refer to “Wiring Precautions” on p. 26 for information about general-purpose cables.
CC-Link Communication
Energy Measuring Unit
Communication Unit
MELSEC
FX Series*
3
MELSEC
Q Series*
3
Current Values Display
CSV File Output
GOT 1000 Series
Logging Unit
CSV Data
Examples of
CSV data screens
The logging unit stores measurement data for
a specified period and outputs it to an SD memory card.*
1
Even data from multiple
energy measuring units
can be managed on
a single SD memory card.*
2
MELSEC-Q Series*
3
Electroronic Multi-Measuring
Instrument
Remote I/O Unit
(CC-Link Communication)
EcoMonitorPro
Energy
Measuring Unit
+ CC-Link
Communication Unit
CC-Link Communication
*3: A unit compatible with MODBUS
®
RTU (RS485) communication is required if connecting with a PLC.
Expansion by use of Logging and Communication Units
3
■Logging Unit
Use of a logging unit allows you to output various energy (such as current, voltage and power) data measured
using the energy measuring unit in CSV file format on an SD memory card for easy data management.
■Communication Unit (CC-Link Communication Unit)
A communication unit can be connected to the system using CC-Link communication.
MODBUS
®
RTU (RS485) Communication as Standard Equipment
2
Providing MODBUS
®
RTU (RS485) communication as standard equipment allows you to connect
with the functions listed below, and use it for energy management and as a system terminal.
①
Host systems (such as PLC, etc.)
②
Data Acquisition Software (EMU4-SW1)*
1
to Special Applications on p.11
③
Display device (GOT)
2
*1: Data Acquisition Software (EMU4-SW1) can be downloaded for free from the Mitsubishi Electric website.
*2: A sample GOT screen can be downloaded for free from the Mitsubishi Electric website. (GT14**-Q, GT1030)
*1: The data retention period of the logging unit is limited.
*2: It is necessary to always specify logging ID when collecting measurement data from multiple logging units on a single SD memory card.
Refer to the operation manual for details.
*3: Units compatible with each communication method are necessary if connecting a PLC.
High Performance Model
・440V direct input
(Three-phase 3-wire compatible)
・277V/480V direct input
(Three-phase 4-wire compatible)
・Measures harmonic current,
voltage, etc.
・Pulse input/output
・Contact input/output
EMU4-HD1-MB
High Performance Model
Host System
Data Acquisition
software
Display Device
(GOT)
MODBUS
®
RTU
(RS485)
Communication
Standard Model
You can use the front panel
operating switches
to specify settings
and change the display.
Displayed on main unit of
measuring unit.
You can measure all types of
energy including power use,
voltage and current.
EMU4-BD1-MB
Standard Model
Summary of Contents for EMU4-BD1-MB