2. Buffer tank control
Buffer tank control operates when heating (or cooling) function is active in the smart grid ready*.
* Refer to the installation manual of indoor unit.
2.1 Wiring for buffer tank control
<Thermistor inputs>
Name
Terminal block
Item
Optional part model
THW6
TBI.5 7-8
Thermistor (Zone1 flow water temp.) (Option)
PAC-TH011-E
THW7
TBI.5 5-6
Thermistor (Zone1 return water temp.) (Option)
THW10
TBI.6 5-6
Thermistor (Mixing tank water temp.)
PAC-TH012HTL-E
<Signal inputs>
Name
Terminal block
Item
OFF (open)
ON (short)
IN11
TBI.3 3-4
Smart grid ready input
IN11
IN12
Meaning
OFF (open) OFF (open) Normal operation
ON (short) OFF (open) Switch-on recommendation
OFF (open) ON (short)
Switch-off command
ON (short) ON (short) Switch-on command
IN12
TBI.3 1-2
2.2 Dip switch setting
Set Dip SW2-6 to ON.
Dip switch
Function
OFF
ON
SW2-6
Mixing tank
WITHOUT Mixing tank
WITH Mixing tank
2.3 Main controller setting
<Service menu> → “Operation settings” → “Smart grid ready”
Name
Description
Heating
Target temp.
Target temp. of "Switch-on recommendation".
Target temp. of "Switch-on command".
Cooling
Target temp.
Target temp. of "Switch-on recommendation".
Target temp. of "Switch-on command".
Pump
cycles
On/Off
When set to "On", the water circulation pump is operated intermittently according
to the heat storage temp. of the buffer tank.
Interval
Re-judgment of the pump on/off time.
Optional parts
D-42
HIGH TEMP. THERMISTOR
6
Optional parts