99
OCH714D
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Parameters
Default
setting
Field
setting Notes
Service
menu
Energy
monitor
settings
Electric heater
capacity
Booster heater 1
capacity
0 to 30 kW
2 kW
Booster heater 2
capacity
0 to 30 kW
4 kW
Immersion heater
capacity
0 to 30 kW
0 kW
Analog output
0 to 30 kW
0 kW
Delivered energy adjustment
−50 to +50%
0%
Water pump input
Pump 1
0 to 200 W or ***(factory fitted pump)
***
Pump 2
0 to 200 W
0 W
Pump 3
0 to 200 W
0 W
Pump 4
0 to 200 W
72 W
Electric energy meter *17
0.1/1/10/100/1000 pulse/kWh
1000 pulse/kWh
Heat meter *17
0.1/1/10/100/1000 pulse/kWh
1000 pulse/kWh
External
input
settings
Demand control (IN4)
Heat source OFF/Boiler operation
Boiler
operation
Outdoor thermostat (IN5)
Heater operation/Boiler operation
Boiler
operation
Thermo ON output
Zone1/Zone2/Zone1&2
Zone1&2
*1 The settings related to Zone2 can be switched only when 2-zone temperature control or 2-Zone valve ON/OFF control is active.
*2 The settings related to Zone2 can be switched only when 2 zone temperature control is enabled (when DIP SW2-6 and SW2-7 are ON).
*3 Cooling mode settings are available for ER model only.
*4 When the cylinder unit is connected with a PUMY-P outdoor unit, the mode is fixed to "Normal".
*5 For the model without both booster and immersion heater, it may not reach the set temperature depending on the outside ambient temperature.
*6 The lower limit is -15°C depending on the connected outdoor unit.
*7 The lower limit is -13°C depending on the connected outdoor unit.
*8 The lower limit is -14°C depending on the connected outdoor unit.
*9 On: the function is active; Off: the function is inactive.
*10 Do not change the setting since it is set according to the specification of flow sensor attached to the cylinder unit.
*11 When DIP SW1-1 is set to OFF “WITHOUT Boiler” or SW2-6 is set to OFF “WITHOUT Mixing tank”, neither Boiler nor Hybrid can be selected.
*12 Valid only when operating in Heating room temperature.
*13 When DIP SW5-2 is set to OFF, the function is active.
*14 If asterisk (**) is chosen freeze stat function is deactivated. (i.e. primary water freeze risk)
*15 When the cylinder unit is connected with a PUMY-P outdoor unit, the mode is fixed to "Ambient".
*16 “*” of “*/kWh” represents currency unit (e.g. € or £ or the like)
*17 The default setting is 1 pulse/kWh depending on the connected indoor unit.